6. FUNCTION AND DATA SETTINGS
Display
Description
Select the volume unit for pulse weight using parameter number "F1".
Code
Volume Unit
00
01
02
03
04
05
06
Volume unit used in 10
-9
×
flow rate span
Volume unit used in 10
-6
×
flow rate span
Volume unit used in 10
-3
×
flow rate span
Volume unit used in 1
×
flow rate span
Volume unit used in 10
3
×
flow rate span
Volume unit used in 10
6
×
flow rate span
Number of pulses output per second at 100% of output
Code
Pulse Width
00
01
02
03
04
05
06
Example : When pulses are to be output per liter in a span of
m
3
/h, select "02" since L(liter) = 10
-3
×
m
3
Set the low cut range percentage in parameter "F3".
Range of setting : 0 to 100% (of span)
Set pulse weight "10 (L)" in parameter number "E2".
Select the pulse width in parameter number "F4".
Select instantaneous flow rate data or damped flow rate data for the pulse
output calculation. (The damped value is the value set in "B2".)
Set parameter "N2" to "01" when the pulse output transistor is to be off active.
Since parameter number "F2" is a 5-digit data item, scrolling is
necessary to display all the data. Mind the decimal point when
setting are made. (The decimal point can be moved if required.)
Default: 01
(Damped flow rate value)
Default: 00(ON ACTIVE)
Default: 3%
Default: 50%DUTY
50%DUTY
(Max. 1000P/s
min. 0.0001P/s)
0.5ms
(Max. 1000P/s
min. 0.0001P/s)
1ms
(Max. 500P/s
min. 0.0001P/s)
20ms
(Max. 25P/s
min. 0.0001P/s)
33ms
(Max. 15P/s
min. 0.0001P/s)
50ms
(Max. 10P/s
min. 0.0001P/s)
100ms
(Max. 5P/s
min. 0.0001P/s)
Normally, these are all required settings. The following settings are made depending on the applications
that are used.
*The "n" item can be opend by entering "55" in paramter number "L2".