8.1.1 Zero Adjustment Using Data Setting Keys
The following two procedures can be used to perform zero adjustment with the data
setting keys.
(1) Hold Down the INC Key for Two Seconds in Flow Rate Data Display Mode.
Display
Description
Code
Content
Call up the setting mode and set "01" in "C1" (zero adjustment enable / disable).
Hold down the INC key for two seconds in flow rate data display mode.
The display panel shows "-ZEro-".
After about 60 seconds, the zero correction is displayed. Then the meter returns to
data display mode.
00
01
Zero adjustment disabled
Zero adjustment enabled
SET SHIFT INC
Default: 01
%
2 seconds
or longer
(2) Display “C2” and Press the SET Key Twice.
Display
Description
Code
Content
Call up the setting mode and set "01" in "C1" (zero adjustment enable/disable).
Call up "C2" and press the SET key twice (as for data entry).
The display panel shows "-ZEro-".
After about 60 seconds, the zero correction is displayed. Then the meter returns to
data display mode.
00
01
Zero adjustment disabled
Zero adjustment enabled
SET SHIFT INC
Twice
60 seconds
later
(Displays the
zero
correction)