IM 1E8B0-01E
6-9
6. FUNCTION AND DATA SETTINGS
6.3.3 Presetting for Totalization Display
• This function is used to reset or preset totalization values of the display unit.
• Hold down the SHIFT key for more than 2 seconds while the totalization values of
the flow rate reading are displayed to set the totalization value to the value set in
parameter number "E5".
Display
Description
Select totalization enable in parameter number "E4"
Code
Description
00
01
Totalization presetting inhibit
Totalization presetting enabled
Set the totalization preset value in parameter number "E5". The initial value
is 0, if it is no setting, the function is zero setting.
Hold down the SHIFT key for more than 2 seconds while the totalization
values of the flow rate reading are displayed to set the totalization value to
the value set in parameter number "E5"
Default: 00 (disabled)
Default: 0
SET SHIFT INC
6.3.4 Damping Time Constant
• The time constant can be changed by setting the parameter No. “02” to suppress a
fluctuation or change a response time.
• The time constant influences to flow rate, pulse output and internal totalization.
However, in case “00” is selected in parameter No. “n1”, the pulse output and internal
totalization are not influenced by it.
Display
Description
Set the value in parameter number "02".
Range of possible settings : 1.0 to 200.0 seconds.
Default: 3 seconds