5 presetting totalization display (refer to 6.3.3), 6 damping time constant (refer to 6.3.4), Damping time constant (refer to 6.3.4) -11 – Yokogawa ADMAG CA User Manual
Page 61
IM 1E8B0-01E
7-11
7. OPERATION VIA BRAIN TERMINAL
7.2.5
Presetting Totalization Display (Refer to 6.3.3)
Display
Description
Code
Description
ENABLE
INHIBIT
Totalization presetting enabled
Totalization presetting inhibit
Select totalization enable in parameter number “E04.”
Set the totalization preset value in parameter number “E05.”
The default is 0 and if the setting is omitted, the parameter functions reset to
0.
If the ENT key is pressed twice while “A30 : TOTAL” is displayed on the
setting screen, the totalization value (A30 : TOTAL) will be replaced with the
values set in “E05.”
ENTER
PARAM
E04:TOTAL SET
ENABLE
E05:TL SET VALUE
0
E10:TL SET UNIT
0
DATA
ESC
DIAG
PARAM
A10:FLOW RATE(%)
50 .0 %
A20:FLOW RATE
50 .0 m
3
/h
A30:TOTAL
12345
DATA
PRNT
ESC
DIAG
SETTING
A30:TOTAL
0
CLR
ESC
7.2.6
Damping Time Constant (Refer to 6.3.4)
Display
Description
Set the value in parameter number "B02."
Range of possible settings : 1.0 to 200.0 seconds.
PARAM
B01:TAG NO
B02:DAMPING
3.0 s
B03:FLOW SPAN
1.00 m/s
DATA
ESC
DIAG
7.2.7
Current Output During Alarm Occurrence (Refer to 6.3.5)
Display
Description
Set the value for current output to be used during alarms in parameter "B11."
(Default : 2.4 mA or less)
2.4mA OR LESS
4.0mA
HOLD
21.6mA OR MORE
2.4 mA or less
4.0 mA
Hold
21.6 mA or more
Content
Code
PARAM
B10:PULSE/ALARM
PULSE OUT
B11:4-20 ALM OUT
2.4mA OR LESS
B12:POWER FREQ
50.03Hz
DATA
ESC
DIAG