beautypg.com

5 presetting totalization display (refer to 6.3.3), 6 damping time constant (refer to 6.3.4), Damping time constant (refer to 6.3.4) -11 – Yokogawa ADMAG CA User Manual

Page 61

background image

IM 1E8B0-01E

7-11

7. OPERATION VIA BRAIN TERMINAL

7.2.5

Presetting Totalization Display (Refer to 6.3.3)

Display

Description

Code

Description

ENABLE

INHIBIT

Totalization presetting enabled

Totalization presetting inhibit

Select totalization enable in parameter number “E04.”

Set the totalization preset value in parameter number “E05.”
The default is 0 and if the setting is omitted, the parameter functions reset to
0.

If the ENT key is pressed twice while “A30 : TOTAL” is displayed on the
setting screen, the totalization value (A30 : TOTAL) will be replaced with the
values set in “E05.”

ENTER

PARAM
E04:TOTAL SET
ENABLE
E05:TL SET VALUE
0
E10:TL SET UNIT
0

DATA

ESC

DIAG

PARAM
A10:FLOW RATE(%)
50 .0 %
A20:FLOW RATE
50 .0 m

3

/h

A30:TOTAL

12345

DATA

PRNT

ESC

DIAG

SETTING
A30:TOTAL
0

CLR

ESC

7.2.6

Damping Time Constant (Refer to 6.3.4)

Display

Description

Set the value in parameter number "B02."
Range of possible settings : 1.0 to 200.0 seconds.

PARAM
B01:TAG NO

B02:DAMPING

3.0 s
B03:FLOW SPAN
1.00 m/s

DATA

ESC

DIAG

7.2.7

Current Output During Alarm Occurrence (Refer to 6.3.5)

Display

Description

Set the value for current output to be used during alarms in parameter "B11."
(Default : 2.4 mA or less)

2.4mA OR LESS

4.0mA

HOLD

21.6mA OR MORE

2.4 mA or less

4.0 mA

Hold

21.6 mA or more

Content

Code

PARAM
B10:PULSE/ALARM
PULSE OUT

B11:4-20 ALM OUT

2.4mA OR LESS
B12:POWER FREQ
50.03Hz

DATA

ESC

DIAG