7. OPERATION VIA BRAIN TERMINAL
7.2.4
Display of Internal Totalization (Refer to 6.3.2)
Example : 10 L (liter) output per pulse in a flow rate span of
ٗٗٗ m
3
/h
Display
Description
Code
Volume unit
n UNIT/P
µ
UNIT/P
m UNIT/P
UNIT/P
k UNIT/P
M UNIT/P
PULSE/s
Volume unit used in 10
-9
×
flow rate span
Volume unit used in 10
-6
×
flow rate span
Volume unit used in 10
-3
×
flow rate span
Volume unit used in 1
×
flow rate span
Volume unit used in 10
3
×
flow rate span
Volume unit used in 10
6
×
flow rate span
Number of pulses output per second at 100% of output
Example) When pulses are to be output per L(liter) in a span of
ٗٗ
m
3
/h, select “m UNIT/P” since a L =10
-3
×
m
3
Set the pulse weight “10 (L)” in parameter number “E02.”
Set the low cut range percentage in parameter “E03.” Range of setting : (0 to
100% of span)
Select instantaneous flow rate or flow rate after damping for the pulse output.
(The damping time value is the value set in “B02.”)
Default: DAMP (damped flow rate data)
Select the volume unit for the pulse weight in parameter number “E01.”
PARAM
E01:TOTAL UNIT
m UNIT/P
E02:TOTAL SCALE
10 m UNIT/P
E03:TOTAL LOWCUT
3. %
DATA
ESC
DIAG
PARAM
N01:TOTAL/PULSE
DAMP
N02:PULSE MODE
ON
N03:RATE LIMIT
5. %
DATA
ESC
DIAG
* The "N" item can be opend by entering "55" in parameter number "L02".