2 zero adjustment via the bt200, Zero adjustment via the bt200 -3 – Yokogawa ADMAG CA User Manual
Page 68
![background image](/manuals/360061/68/background.png)
IM 1E8B0-01E
8-3
8. ACTUAL OPERATION
8.1.2 Zero Adjustment Via the BT200
Setting displayed
Description
Call up the menu screen and select "C:ADJUST"
Press the ENTER key to call the screen displaying the parameter sub items. Move
the inverse video bar to C02:MAGFLOW ZERO
Pressing the ENTER key causes the data setup screen to be displayed. If the
security screen is displayed, enter the security code.
While "C02:MAGFLOW ZERO" is displayed, press the ENTER key once, then
wait a few seconds and press again.
"AUTO ZERO" is now displayed
After about 60 seconds, press the "F4" of the Function key causes the Menu screen
to be displayed. The zero correction is displayed. Then the meter returns to data
display mode.
CLR
DATA
DATA
MENU
A:DISPLAY
B:SET
C:ADJUST
D:DISP SEL
E:TOTAL SET
F:PULSE SET
ESC
SET
ADJ
DIAG
HOME
PARAM
C01:ZERO TUNING
ENABLE
C02:MAGFLOW ZERO
0 .05
C60:SELF CHECK
GOOD
ESC
DIAG
CLR
DATA
SET
C02:MAGFLOW ZERO
0.05
+ 00.05
ESC
DIAG
DIAG
SET
C02:MAGFLOW ZERO
AUTOZERO
OK
NO
FEED
DIAG
PARAM
C01:ZERO TUNING
ENABLE
C02:MAGFLOW ZERO
0 .02
C60:SELF CHECK
GOOD
ESC
DATA
*For entry of the security code, see IM ICA11-0IE