7. OPERATION VIA BRAIN TERMINAL
7.2.13 Rate Limit (Refer to 6.3.11)
Display
Description
Set the rate limit value in parameter number "N03." Range of possible settings: 0
to 10%.
Set the dead time in parameter number "N04."
Range of possible settings: 0 to 15 seconds.
Default: 0
(Rate limit function off)
PARAM
N03:RATE LIMIT
5 %
N04:DEAD TIME
0 s
N05:POWER SYNCH
YES
DATA
ESC
DIAG
DATA
ESC
DIAG
* The "N" item can be opend by entering "55" in parameter number "L02".
7.2.14 User-Defined Units
This function displays the instantaneous flow rate indicated in "A20 FLOW RATE" in
units other than those selectable with B04. If the specific gravity of the fluid is known,
the instantaneous flow rate can be displayed in weight units.
(1) User-Defined units for Instantaneous Flow Rate
Example:
Displaying the flow rate of a fluid (its specific gravity is 2) in weight (kg)
in a flow rate span of 10m
3
/h. When the flow rate is 100%, 20,000kg is
displayed.
Display
Description
Select "PROVIDED" in "D02."
For item "D03," set the value to be displayed in "A20 FLOW RATE" when the
flow rate is 100% in the span set in "B03FLOW SPAN." Set the unit in "D10".
Set the user-defind unit in "D10."
The maximum flow rate value of 20,000 kg is displayed as the instantaneous
flow rate in "A20 : FLOWRATE."
PARAM
D02:FL USER SEL
PROVIDED
D03:FL USER SPAN
20000.0
D10:FL USER UNIT
kg/h
DATA
ESC
DIAG
DATA
ESC
DIAG
PARAM
A10:FLOW RATE(%)
100.0%
A20:FLOW RATE
20000.0 kg/h
A30:TOTAL
12345
DATA
ESC
DIAG
DATA
ESC
DIAG