Diagnostics menu, Calibration menu, Diagnostics menu calibration menu – Watlow EZ-ZONE RM-Scanner-Modul User Manual
Page 87
Watlow EZ-ZONE
®
RMS Module
•
84
•
Chapter 5 Factory Page
RM Scanner Module • Factory Page
Display
Parameter Name
Description
Range
Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Parameter
ID
Data
Type
& Read/
Write
[diAg]
[FCty]
Diagnostics Menu
[``Pn]
[ Pn]
Diagnostics Menu
Part Number
Display this controller's part
number.
24
- - - -
0x65
(101)
1
9
90
1009
string
R
No Dis-
play
Diagnostics Menu
Device Name
Read the device name.
EZ-ZONE RM
- - - -
- - - -
0x65
(101)
1
0x0B (11)
- - - -
1011
string
R
No Dis-
play
Diagnostics Menu
Device Status
Return hardware status
Fail means return to factory.
OK (138)
Fail (32)
- - - -
30
0x65
(101)
1
0x10 (16)
- - - -
1016
uint
R
[`rEu]
[ rEu]
Diagnostics Menu
Software Revision
Display this controller's firm-
ware revision number.
5
- - - -
4
0x65
(101)
1 to 5
0x11 (17)
91
1017
string
R
[S;bLd]
[S.bLd]
Diagnostics Menu
Software Build Number
Display the firmware build
number.
- - - -
- - - -
8
0x65
(101)
1 to 5
5
- - - -
1005
signed
32-bit
R
[``Sn]
[ Sn]
Diagnostics Menu
Serial Number
Display the serial number.
- - - -
- - - -
12
0x65
(101)
1
7
- - - -
1007
signed
32-bit
R
[dAtE]
[dAtE]
Diagnostics Menu
Date of Manufacture
Display the date code in YY-
WW format
- - - -
- - - -
14
0x65
(101)
1
8
- - - -
1008
signed
32-bit
R
No Dis-
play
Diagnostics Menu
Hardware ID
Read the hardware ID.
115
115
0
0x65
(101)
1
1
- - - -
1001
signed
32-bit
R
[`CAL]
[FCty]
Calibration Menu
[`Mu]
[ Mv]
Calibration Menu (1 to 16)
Electrical Measurement
Read the raw electrical value
for this input in the units cor-
responding to the Sensor Type
(Setup Page, Analog Input
Menu) setting.
- - - -
420
[offset
90]
0x68
(104)
1 to 0x0C
(12)
0x15 (21)
- - - -
4021
float
R
[ELi;o]
[ELi.o]
Calibration Menu (1 to 16)
Electrical Input Offset
Change this value to calibrate
the low end of the input range.
-1,999.000 to 9,999.000
0.0
398
[offset
90]
0x68
(104)
1 to 0x0C
(12)
0xA (10)
- - - -
4010
float
RWES
[ELi;S]
[ELi.S]
Calibration Menu (1 to 16)
Electrical Input Slope
Adjust this value to calibrate
the slope of the input value.
-1,999.000 to 9,999.000
1.0
400
[offset
90]
0x68
(104)
1 to 0x0C
(12)
0xB (11)
- - - -
4011
float
RWES
Note: Some values will be rounded off to fit in the four-character display . Full values can
be read with another interface .
If there is only one instance of a menu, no submenus will appear .
R: Read
W: Write
E: EE-
PROM
S: User
Set