Chapter 5 Factory Page

RM Scanner Module • Factory Page

Display

Parameter Name

Description

Range

Default

Modbus

Relative

Address

CIP

Class

Instance

Attribute

hex (dec)

Profibus

Index

Parameter

ID

Data

Type

& Read/

Write

[diAg]
[FCty]
Diagnostics Menu

[``Pn]
[ Pn]

Diagnostics Menu

Part Number

Display this controller's part

number.

24

- - - -

0x65

(101)

1

9

90

1009

string

R

No Dis-

play

Diagnostics Menu

Device Name

Read the device name.

EZ-ZONE RM

- - - -

- - - -

0x65

(101)

1

0x0B (11)

- - - -

1011

string

R

No Dis-

play

Diagnostics Menu

Device Status

Return hardware status

Fail means return to factory.

OK (138)

Fail (32)

- - - -

30

0x65

(101)

1

0x10 (16)

- - - -

1016

uint

R

[`rEu]
[ rEu]

Diagnostics Menu

Software Revision

Display this controller's firm-

ware revision number.

5

- - - -

4

0x65

(101)

1 to 5

0x11 (17)

91

1017

string

R

[S;bLd]
[S.bLd]

Diagnostics Menu

Software Build Number

Display the firmware build

number.

- - - -

- - - -

8

0x65

(101)

1 to 5

5

- - - -

1005

signed

32-bit

R

[``Sn]
[ Sn]

Diagnostics Menu

Serial Number

Display the serial number.

- - - -

- - - -

12

0x65

(101)

1

7

- - - -

1007

signed

32-bit

R

[dAtE]
[dAtE]

Diagnostics Menu

Date of Manufacture

Display the date code in YY-

WW format

- - - -

- - - -

14

0x65

(101)

1

8

- - - -

1008

signed

32-bit

R

No Dis-

play

Diagnostics Menu

Hardware ID

Read the hardware ID.

115

115

0

0x65

(101)

1

1

- - - -

1001

signed

32-bit

R

[`CAL]
[FCty]
Calibration Menu

[`Mu]
[ Mv]

Calibration Menu (1 to 16)

Electrical Measurement

Read the raw electrical value

for this input in the units cor-

responding to the Sensor Type

(Setup Page, Analog Input

Menu) setting.

- - - -

420

[offset

90]

0x68

(104)

1 to 0x0C

(12)

0x15 (21)

- - - -

4021

float

R

[ELi;o]
[ELi.o]

Calibration Menu (1 to 16)

Electrical Input Offset

Change this value to calibrate

the low end of the input range.

-1,999.000 to 9,999.000

0.0

398

[offset

90]

0x68

(104)

1 to 0x0C

(12)

0xA (10)

- - - -

4010

float

RWES

[ELi;S]
[ELi.S]

Calibration Menu (1 to 16)

Electrical Input Slope

Adjust this value to calibrate

the slope of the input value.

-1,999.000 to 9,999.000

1.0

400

[offset

90]

0x68

(104)

1 to 0x0C

(12)

0xB (11)

- - - -

4011

float

RWES

Note: Some values will be rounded off to fit in the four-character display . Full values can
be read with another interface .

If there is only one instance of a menu, no submenus will appear .

R: Read

W: Write

E: EE-

PROM

S: User

Set