Watlow EZ-ZONE

®

RMS Module

58

Chapter 4 Setup Page

RM Scanner Module

Setup Page

Display

Parameter Name

Description

Range

Default

Modbus

Relative

Address

CIP

Class

Instance

Attribute

hex (dec)

Profibus

Index

Parameter

ID

Data

Type

&

Read/

Write

[`A;Si]
[ A.Si]

Alarm (1 to 16)

Silencing

Turn alarm silencing on to

allow the user to disable

this alarm.

[`oFF]

Off (62)

[``on]

On (63)

Off

2510

[offset 60]

0x6D

(109)

1 to 0x10

(16)

6

29

9006

uint
RWES

[A;dSP]
[A.dSP]

Alarm (1 to 16)

Display

Display an alarm message

when an alarm is active.

[`oFF]

Off (62)

[``on]

On (63)

On

2530

[offset 60]

0x6D

(109)

1 to 0x10

(16)

0x10 (16)

30

9016

uint
RWES

[`A;dL]
[ A.dL]

Alarm (1 to 16)

Delay Time

Set the span of time that

the alarm will be delayed

after the process value ex-

ceeds the alarm set point.

0 to 9,999 seconds

0

2540

[offset 60]

0x6D

(109)

1 to 0x10

(16)

0x15 (21)

31

9021

uint
RWES

[A;Clr]
[ A.hi]

Alarm (1 to 16)

Clear Request

Select Clear to clear alarm

once in safe region.

Note:

This prompt is not avail-

able unless alarm latch-

ing is set to latching.

Clear (129)

Ignore (204)

Ignore

- - - -

- - - -

- - - -

9026

uint
RW

[A;sir]
[A.Sir]

Alarm (1 to 16)

Silence Request

Select Silence to silence

alarm while in fail region.

Note:

This prompt is not avail-

able unless alarm silenc-

ing is set to on.

Ignore (204)
Silence (108)

Ignore

- - - -

- - - -

- - - -

9027

uint
RW

[`A;st]
[ A.St]

Alarm (1 to 16)

State

View state of alarm

Startup (88)
None (61)
Blocked (12)
Alarm Low (8)
Alarm High (7)
Error (28)

Startup

- - - -

- - - -

- - - -

9009

uint
R

[`Lnr]
[`Set]
Linearization Menu

[``Fn]
[ Fn]

Linearization (1 to 24)

Function

Set how this function will

linearize Source A.

[`oFF]

Off (62)

[intr]

Interpolated (1482)

[Stpd]

Stepped (1483)

Off

11348

[offset 70]

0x86 (134)

1 to 0x18

(24)

5

86

34005

uint
RWES

Note: Some values will be rounded off to fit in the four-character display .
Full values can be read with other interfaces .

If there is only one instance of a menu, no submenus will appear .

R: Read

W: Write

E:

EEPROM

S:

User

Set