Chapter 4 Setup Page

RM Scanner Module

Setup Page

Display

Parameter Name

Description

Range

Default

Modbus

Relative

Address

CIP

Class

Instance

Attribute

hex (dec)

Profibus

Index

Parameter

ID

Data

Type

&

Read/

Write

[`o;Ct]
[ o.Ct]

Digital Output (1 to 12)

Control

Set the output control type.

This parameter is only

used with PID control, but

can be set anytime.

[`Ftb]

Fixed Time Base (34)

[`utb]

Variable Time Base

(103)

Fixed

Time

Base

1822

[offset 30]

0x6A

(106)

1 to 0x0C

(12)

2

41

6002

uint

RWES

[`o;tb]
[ o.tb]

Digital Output (1 to 12)

Time Base

Set the time base for

fixed-time-base control in

seconds.

0.1 to 60.0 for switched DC

1.0

1824

[offset 30]

0x6A

(106)

1 to 0x0C

(12)

3

42

6003

float

RWES

[`o;Lo]
[ o.Lo]

Digital Output (1 to 12)

Low Power Scale

The power output will nev-

er be less than the value

specified and will represent

the value at which output

scaling begins.

0.0 to 100.0

0.0

1836
[offset 30]

0x6A

(106)

1 to 0x0C

(12)

9

43

6009

float
RWES

[`o;hi]
[ o.hi]

Digital Output (1 to 12)

High Power Scale

The power output will

never be greater than the

value specified and will

represent the value at

which output scaling stops.

0.0 to 100.0

100.0

1838
[offset 30]

0x6A

(106)

1 to 0x0C

(12)

0xA (10)

44

6010

float
RWES

[`ACt]
[`SEt]
Action Menu

[``Fn]
[ Fn]

Action (1 to 16)

Function

Set the action that will be

triggered by this function.

[nonE]

None (61)

[USr;r]

User Restore (227)

[ALM]

Alarm Reset (6)

[`SiL]

Silence Alarms (108)

[`AoF]

Loop alarms Off

(220)

[`F;AL]

Force Alarm to Occur

(218)

None

2184
[offset 20]

0x6E

(110)

1 to 0x10

(16)

3

79

10003

uint
RWES

[``Fi]
[ Fi]

Action (1 to 16)

Function Instance

Set the instance of the

function selected above.

0 to 25

0

2186
[offset 20]

0x6E

(110)

1 to 0x10

(16)

4

80

10004

uint
RWES

Note: Some values will be rounded off to fit in the four-character display .
Full values can be read with other interfaces .

If there is only one instance of a menu, no submenus will appear .

R: Read

W: Write

E:

EEPROM

S:

User

Set