beautypg.com

Communications menu – Watlow EZ-ZONE RM-Scanner-Modul User Manual

Page 83

background image

Watlow EZ-ZONE

®

RMS Module

80

Chapter 4 Setup Page

RM Scanner Module

Setup Page

Display

Parameter Name

Description

Range

Default

Modbus

Relative

Address

CIP

Class

Instance

Attribute

hex (dec)

Profibus

Index

Parameter

ID

Data

Type

&

Read/

Write

[USr;S]
[USr.S]

Global

User Settings Save

Save all of this controller's

settings to the selected

set.

[none]

None (61)

[SEt1]

User Set 1 (101)

Note:

Starting with firmware

version 6.0, there is only

one user set.

None

26

0x65 (101)

1

0x0E (14)

59

1014

uint

W

[USr;r]
[USr.r]

Global

User Settings Restore

Replace all of the control-

ler's settings with another

set previously saved.

[none]

None (61)

[SEt1]

User Set 1 (101)

[FCty]

Factory (31)

Note:

Starting with firmware

version 6.0, there is only

one user set.

None

24

0x65 (101)

1

0x0D (13)

58

1013

uint

W

[CoM]
[`SEt]
Communications Menu

[bAUd]
[bAUd]

Communications

Baud Rate

Set the speed of this con-

troller's communications

to match the speed of the

serial network.

9,600 (188)
19,200 (189)
38,400 (190)

9,600

3464

0x96 (150)

1

3

- - - -

17002

uint
RWE

[`PAr]
[ PAr]

Communications

Parity

Set the parity of this con-

troller to match the parity

of the serial network.

[none]

None (61)

[EuEn]

Even (191)

[`odd]

Odd (192)

None

3466

0x96 (150)

1

4

- - - -

17003

uint
RWE

[M;hL]
[M.hL]

Communications

Modbus Word Order

Select the word order of

the two 16-bit words in the

floating-point values.

[hiLo]

Word High Low

(1330)

[Lohi]

Word Low High

(1331)

Low High 3468

0x96 (150)

1

5

- - - -

17043

uint
RWE

[`C_F]
[ C_F]

Communications

Display Units

Select which scale to use for

temperature over comms.

°F (30)
°C (15)

°F

3470

0x96 (150)

1

6

113

17050

uint
RWE

[`nU;S]
[ nV.S]

Communications (1)

Non-volatile Save

If set to Yes all values writ-

ten to the control will be

saved in EEPROM.

Note:

Any value that is changed

from the RUI or over a

communications port will

initiate a write to the EE-

PROM. Life of EEPROM

is approximately one mil-

lion writes.

[`yes]

Yes (106)

[``no]

No (59)

Yes

3474

0x96 (150)

1

8

112

17051

uint
RWE

Note: Some values will be rounded off to fit in the four-character display .
Full values can be read with other interfaces .

If there is only one instance of a menu, no submenus will appear .

R: Read

W: Write

E:

EEPROM

S:

User

Set