Communications menu – Watlow EZ-ZONE RM-Scanner-Modul User Manual
Page 83
Watlow EZ-ZONE
®
RMS Module
•
80
•
Chapter 4 Setup Page
RM Scanner Module
•
Setup Page
Display
Parameter Name
Description
Range
Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Parameter
ID
Data
Type
&
Read/
Write
[USr;S]
[USr.S]
Global
User Settings Save
Save all of this controller's
settings to the selected
set.
[none]
None (61)
[SEt1]
User Set 1 (101)
Note:
Starting with firmware
version 6.0, there is only
one user set.
None
26
0x65 (101)
1
0x0E (14)
59
1014
uint
W
[USr;r]
[USr.r]
Global
User Settings Restore
Replace all of the control-
ler's settings with another
set previously saved.
[none]
None (61)
[SEt1]
User Set 1 (101)
[FCty]
Factory (31)
Note:
Starting with firmware
version 6.0, there is only
one user set.
None
24
0x65 (101)
1
0x0D (13)
58
1013
uint
W
[CoM]
[`SEt]
Communications Menu
[bAUd]
[bAUd]
Communications
Baud Rate
Set the speed of this con-
troller's communications
to match the speed of the
serial network.
9,600 (188)
19,200 (189)
38,400 (190)
9,600
3464
0x96 (150)
1
3
- - - -
17002
uint
RWE
[`PAr]
[ PAr]
Communications
Parity
Set the parity of this con-
troller to match the parity
of the serial network.
[none]
None (61)
[EuEn]
Even (191)
[`odd]
Odd (192)
None
3466
0x96 (150)
1
4
- - - -
17003
uint
RWE
[M;hL]
[M.hL]
Communications
Modbus Word Order
Select the word order of
the two 16-bit words in the
floating-point values.
[hiLo]
Word High Low
(1330)
[Lohi]
Word Low High
(1331)
Low High 3468
0x96 (150)
1
5
- - - -
17043
uint
RWE
[`C_F]
[ C_F]
Communications
Display Units
Select which scale to use for
temperature over comms.
°F (30)
°C (15)
°F
3470
0x96 (150)
1
6
113
17050
uint
RWE
[`nU;S]
[ nV.S]
Communications (1)
Non-volatile Save
If set to Yes all values writ-
ten to the control will be
saved in EEPROM.
Note:
Any value that is changed
from the RUI or over a
communications port will
initiate a write to the EE-
PROM. Life of EEPROM
is approximately one mil-
lion writes.
[`yes]
Yes (106)
[``no]
No (59)
Yes
3474
0x96 (150)
1
8
112
17051
uint
RWE
Note: Some values will be rounded off to fit in the four-character display .
Full values can be read with other interfaces .
If there is only one instance of a menu, no submenus will appear .
R: Read
W: Write
E:
EEPROM
S:
User
Set