Chapter 4 Setup Page
RM Scanner Module
•
Setup Page
Display
Parameter Name
Description
Range
Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Parameter
ID
Data
Type
&
Read/
Write
[`iP;3]
[ ip.3]
Linearization (1 to 24)
Input Point 3
Set the value that will be
mapped to output 3.
-1,999.000 to 9,999.000 °F or
units
-1,128.333 to 5537.223 °C
2.0
11358
[offset 70]
0x86 (134)
1 to 0x18
(24)
0xA (10)
92
34010
float
RWES
[`oP;3]
[ op.3]
Linearization (1 to 24)
Output Point 3
Set the value that will be
mapped to input 3.
-1,999.000 to 9,999.000 °F or
units
-1,128.333 to 5537.223 °C
2.0
11378
[offset 70]
0x86 (134)
1 to 0x18
(24)
0x14 (20)
93
34020
float
RWES
[`iP;4]
[ ip.4]
Linearization (1 to 24)
Input Point 4
Set the value that will be
mapped to output 4.
-1,999.000 to 9,999.000 °F or
units
-1,128.333 to 5537.223 °C
3.0
11360
[offset 70]
0x86 (134)
1 to 0x18
(24)
0xB (11)
94
34011
float
RWES
[`oP;4]
[ op.4]
Linearization (1 to 24)
Output Point 4
Set the value that will be
mapped to input 4.
-1,999.000 to 9,999.000 °F or
units
-1,128.333 to 5537.223 °C
3.0
11380
[offset 70]
0x86 (134)
1 to 0x18
(24)
0x15 (21)
95
34021
float
RWES
[`iP;5]
[ ip.5]
Linearization (1 to 24)
Input Point 5
Set the value that will be
mapped to output 5.
-1,999.000 to 9,999.000 °F or
units
-1,128.333 to 5537.223 °C
4.0
11362
[offset 70]
0x86 (134)
1 to 0x18
(24)
0xC (12)
96
34012
float
RWES
[`oP;5]
[ op.5]
Linearization (1 to 24)
Output Point 5
Set the value that will be
mapped to input 5.
-1,999.000 to 9,999.000 °F or
units
-1,128.333 to 5537.223 °C
4.0
11382
[offset 70]
0x86 (134)
1 to 0x18
(24)
0x16 (22)
97
34022
float
RWES
[`iP;6]
[ ip.6]
Linearization (1 to 24)
Input Point 6
Set the value that will be
mapped to output 6.
-1,999.000 to 9,999.000 °F or
units
-1,128.333 to 5537.223 °C
5.0
11364
[offset 70]
0x86 (134)
1 to 0x18
(24)
0xD (13)
98
34013
float
RWES
[`oP;6]
[ op.6]
Linearization (1 to 24)
Output Point 6
Set the value that will be
mapped to input 6.
-1,999.000 to 9,999.000 °F or
units
-1,128.333 to 5537.223 °C
5.0
11384
[offset 70]
0x86 (134)
1 to 0x18
(24)
0x17 (23)
99
34023
float
RWES
[`iP;7]
[ ip.7]
Linearization (1 to 24)
Input Point 7
Set the value that will be
mapped to output 7.
-1,999.000 to 9,999.000 °F or
units
-1,128.333 to 5537.223 °C
6.0
11366
[offset 70]
0x86 (134)
1 to 0x18
(24)
E (14)
100
34014
float
RWES
[`oP;7]
[ op.7]
Linearization (1 to 24)
Output Point 7
Set the value that will be
mapped to input 7.
-1,999.000 to 9,999.000 °F or
units
-1,128.333 to 5537.223 °C
6.0
11386
[offset 70]
0x86 (134)
1 to 0x18
(24)
0x18 (24)
101
34024
float
RWES
[`iP;8]
[ ip.8]
Linearization (1 to 24)
Input Point 8
Set the value that will be
mapped to output 8.
-1,999.000 to 9,999.000 °F or
units
-1,128.333 to 5537.223 °C
7.0
11368
[offset 70]
0x86 (134)
1 to 0x18
(24)
0xF (15)
102
34015
float
RWES
[`oP;8]
[ op.8]
Linearization (1 to 24)
Output Point 8
Set the value that will be
mapped to input 8.
-1,999.000 to 9,999.000 °F or
units
-1,128.333 to 5537.223 °C
7.0
11388
[offset 70]
0x86 (134)
1 to 0x18
(24)
0x19 (25)
103
34025
float
RWES
[`iP;9]
[ ip.9]
Linearization (1 to 24)
Input Point 9
Set the value that will be
mapped to output 9.
-1,999.000 to 9,999.000 °F or
units
-1,128.333 to 5537.223 °C
8.0
11370
[offset 70]
0x86 (134)
1 to 0x18
(24)
0x10 (16)
104
34016
float
RWES
Note: Some values will be rounded off to fit in the four-character display .
Full values can be read with other interfaces .
If there is only one instance of a menu, no submenus will appear .
R: Read
W: Write
E:
EEPROM
S:
User
Set