Watlow EZ-ZONE

®

RMS Module

27

Chapter 2 Install and Wire

Warning:

ç

Use National Electric (NEC) or other
country-specific standard wiring and
safety practices when wiring and
connecting this controller to a power
source and to electrical sensors or pe-
ripheral devices. Failure to do so may
result in damage to equipment and
property, and/or injury or loss of life.

Note:

Maximum wire size termination and

torque rating:
• 0.0507 to 3.30 mm2 (30 to 12 AWG)
single-wire termination or two 1.31
mm2 (16 AWG)
• 0.8 Nm (7.0 in-lb.) torque

Note:

Adjacent terminals may be labeled
differently, depending on the model
number.

Note:

To prevent damage to the controller,
do not connect wires to unused ter-
minals.

Note:

Maintain electrical isolation between
digital input-outputs, switched dc/open
collector outputs and process outputs

to prevent ground loops.

Warning:

ç

Explosion Hazard – Substitution of
component may impair suitability for
CLASS I, DIVISION 2.

Warning:

ç

Explosion Hazard - Do not disconnect
while the circuit is live or unless the
area is known to be free of ignitable
concentrations of flammable sub-
stances.

Open Collector Wiring Example Using DO 1-12

VDC

Collector Outputs

Internal Circuitry

Power Supply

5 to 32 VDC

Relay

+

-

Common

Internal Supply

Diode

Fuse

An example fuse is

Bussmann AGC-1 1/2

B_

Z_

D_

D_

D_

D_

D_

D_

As an open collector output (see graphic below), use an external power sup-

ply with the negative wired to B_, the positive to the coil of a pilot mechani-

cal relay and the other side of the coil wired to the output of choice (D_).

Each open collector output can sink 1.5 A with the total for all open collector

outputs not exceeding 8 amperes. Ensure that a kickback diode is reversed

wired across the relay coil to prevent damage to the internal transistor.

Output 1 - 4 and 7 - 10 Mechanical Relay, Form A

RMS Part # Digit 7, 8 is J

normally open

common

L1
K1
L2
K2
L3
K3
L4
K4

Slot D

normally open

common

normally open

common

normally open

common

normally open

common

L7
K7
L8
K8
L9
K9
L10
K10

Slot E

normally open

common

normally open

common

normally open

common

• 5 A at 240VÅ (ac) or 30VÎ

(dc) maximum resistive

load

• 20 mA at 24V minimum

load

• 125 VA pilot duty @

120/240VÅ (ac), 25 VA at

24VÅ (ac)

• 100,000 cycles at rated load
• Output does not supply

power.

• for use with ac or dc
See Quencharc note.
- Slot D Outputs 1 - 6
RMSx-xx(J)x-xxxx

- Slot E Outputs 7 - 10
RMSx-xxx(J)-xxxx

Mechanical Relay Form A

L_

K_

Internal Circuitry


Suppressor Note:
Switching pilot duty inductive loads
(relay coils, solenoids, etc .) with the
mechanical relay, solid-state relay or
open collector output options requires
use of an R .C . suppressor for AC load or
a diode for a DC load .