Watlow EZ-ZONE

®

RMS Module

61

Chapter 4 Setup Page

RM Scanner Module

Setup Page

Display

Parameter Name

Description

Range

Default

Modbus

Relative

Address

CIP

Class

Instance

Attribute

hex (dec)

Profibus

Index

Parameter

ID

Data

Type

&

Read/

Write

[`oP;9]
[ op.9]

Linearization (1 to 24)

Output Point 9

Set the value that will be

mapped to input 9.

-1,999.000 to 9,999.000 °F or

units

-1,128.333 to 5537.223 °C

8.0

11390

[offset 70]

0x86 (134)

1 to 0x18

(24)

0x1A (26)

105

34026

float
RWES

[iP;10]
[ip.10]

Linearization (1 to 24)

Input Point 10

Set the value that will be

mapped to output 10.

-1,999.000 to 9,999.000 °F or

units

-1,128.333 to 5537.223 °C

9.0

11372

[offset 70]

0x86 (134)

1 to 0x18

(24)

0x11 (17)

106

34017

float
RWES

[oP;10]
[op.10]

Linearization (1 to 24)

Output Point 10

Set the value that will be

mapped to input 10.

-1,999.000 to 9,999.000 °F or

units

-1,128.333 to 5537.223 °C

9.0

11392

[offset 70]

0x86 (134)

1 to 0x18

(24)

0x1B (27)

107

34027

float
RWES

[`CPE]
[`Set]
Compare Menu

[``Fn]
[ Fn]

Compare (1 to 24)

Function

Set operator that will be

used to compare Source A

to Source B.

[`oFF]

Off (62)

[``g;t]

Greater Than (1435)

[``L;t]

Less Than (1436)

[```E]

Equal To (1437)

[``nE]

Not Equal To (1438)

[`goE]

Greater or Equal

(1439)
[`LoE]

Less or Equal (1440)

Off

8236

[offset 40]

0x80 (128)

1 to 0x18

(24)

9

137

28009

uint
RWES

[`toL]
[ toL]

Compare (1 to 24)

Tolerance

If the difference between

Source A and Source B is

less than this value the two

will appear to be equal.

0 to 9,999.000

0.1

8240

[offset 40]

0x80 (128)

1 to 0x18

(24)

0xB (11)

138

28011

float
RWES

[SFn;A]
[SFn.A]

Compare (1 to 24)

Source Function A

Set the type of function

that will be used for this

source.

[nonE]

None (61)

[``Ai]

Analog Input (142)

[CUrr]

Current (22)

[`C;Pr]

Cool Power, Control

Loop (161)

[`h;Pr]

Heat Power, Control

Loop (160)

[PWr]

Power, Control Loop

(73)

[`Lnr]

Linearization (238)

[MAt]

Math (240)

[``Pu]

Process Value (241)

[`SP;C]

Set Point Closed,

Control Loop (242)

[`SP;o]

Set Point Open, Con-

trol Loop (243)

[`uAr]

Variable (245)

None

8220

[offset 40]

0x80 (128)

1 to 0x18

(24)

1

- - - -

28001

uint
RWES

[`Si;A]
[ Si.A]

Compare (1 to 24)

Source Instance A

Set the instance of the

function selected above.

1 to 250

1

8224

[offset 40]

0x80 (128)

1 to 0x18

(24)

3

- - - -

28003

uint
RWES

Note: Some values will be rounded off to fit in the four-character display .
Full values can be read with other interfaces .

If there is only one instance of a menu, no submenus will appear .

R: Read

W: Write

E:

EEPROM

S:

User

Set