Display
Parameter Name
Description
Range
Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Parameter
ID
Data
Type
& Read/
Write
[``o;u]
[ o.v]
Logic (1 to 24)
Output Value
View the value of this
function's output.
[`off]
Off (62)
[``on]
On (63)
6366
[offset 80]
0x7F
(127)
1 to 0x18
(24)
0x22 (34)
- - - -
27034
uint
R
No Dis-
play
Logic (1 to 24)
Error
Read reported cause for
logic error
None (61)
Open (65)
Shorted (127)
Measurement Error (140)
Bad Cal Data (139)
Ambient Error (9)
RTD Error (141)
Fail (32)
Math Error (1423)
Not Sourced (246)
Stale (1617)
6370
[offset 80]
0x7F
(127)
1 to 0x18
(24)
0x24 (36)
- - - -
27036
uint
R
[MAt]
[oPEr]
Math Menu
[`Su;A]
[ Su.A]
Math (1 to 24)
Source Value A
View the value of Source
A.
-1,999.000 to 9,999.000°F
or units
-1,128.000 to 5,537.000°C
3530
[offset 70]
0x7D
(125)
1 to 0x18
(24)
0x10 (16)
- - - -
25016
float
RWES
[`Su;b]
[ Su.b]
Math (1 to 24)
Source Value B
View the value of Source
B.
-1,999.000 to 9,999.000°F
or units
-1,128.000 to 5,537.000°C
3532
[offset 70]
0x7D
(125)
1 to 0x18
(24)
0x11 (17)
- - - -
25017
float
RWES
[`Su;C]
[ Su.C]
Math (1 to 24)
Source Value C
View the value of Source
C.
-1,999.000 to 9,999.000°F
or units
-1,128.000 to 5,537.000°C
3534
[offset 70]
0x7D
(125)
1 to 0x18
(24)
0x12 (18)
- - - -
25018
float
RWES
[`Su;d]
[ Su.d]
Math (1 to 24)
Source Value D
View the value of Source
D.
-1,999.000 to 9,999.000°F
or units
-1,128.000 to 5,537.000°C
3536
[offset 70]
0x7D
(125)
1 to 0x18
(24)
0x13 (19)
- - - -
25019
float
RWES
[`Su;E]
[ Su.E]
Math (1 to 24)
Source Value E
View the value of Source
E.
[`off]
Off (62)
[``on]
On (63)
3538
[offset 70]
0x7D
(125)
1 to 0x18
(24)
0x14 (20)
- - - -
25020
uint
RWES
[oFSt]
[oFSt]
Math (1 to 24)
Offset
Set an offset to be applied
to this function's output.
-1,999.000 to 9,999.000°F
or units
-1,128.000 to 5,537.000°C
0
3544
[offset 70]
0x7D
(125)
1 to 0x18
(24)
0x17 (23)
- - - -
25023
float
RWES
[``o;u]
[ o.v]
Math (1 to 24)
Output Value
View the value of this
function's output.
-1,999.000 to 9,999.000°F
or units
-1,128.000 to 5,537.000°C
3542
[offset 70]
0x7D
(125)
1 to 0x18
(24)
0x16 (22)
- - - -
25022
float
RWES
Note: Some values will be rounded off to fit in the four-character display . Full values
can be read with other interfaces .
If there is only one instance of a menu, no submenus will appear .
R: Read
W: Write
E: EEPROM
S: User Set