Watlow EZ-ZONE

®

RMS Module

51

Chapter 4 Setup Page

RM Scanner Module

Setup Page

Display

Parameter Name

Description

Range

Default

Modbus

Relative

Address

CIP

Class

Instance

Attribute

hex (dec)

Profibus

Index

Parameter

ID

Data

Type

&

Read/

Write

[p;unt]
[P.unt]

Process Value (1 to 16)

Pressure Units

Set the units that will be

applied to the source.

[`psi]

Pounds per Square

Inch (1671)

[mbr]

Millibar (1672)

[torr]

Torr (1673)

[pasc]

Pascal (1674)

[atm]

Atmosphere (1675)

PSI

5234

[offset 70]

0x7E

(126)

1 to 0x10

(16)

0x1C (28)

- - - -

26028

uint

RWES

[a;unt]
[A.unt]

Process Value (1 to 16)

Altitude Units

Set the units that will be

applied to the source.

[`Hft]

Kilofeet (1677)

[``ft]

Feet (1676)

HFt

5236

[offset 70]

0x7E

(126)

1 to 0x10

(16)

0x1D (29)

- - - -

26029

uint

RWES

[`b;pr]
[ b.Pr]

Process Value (1 to 16)

Barometric Pressure

Set the units that will be

applied to the source.

10.0 to 16.0

14.7

5238

[offset 70]

0x7E

(126)

1 to 0x10

(16)

0x1E (30)

- - - -

26030

float

RWES

[`Fil]
[ FiL]

Process Value (1 to 16)

Filter

Filtering smooths out the

output signal of this func-

tion block. Increase the

time to increase filtering.

0.0 to 60.0 seconds

0.0

5230

[offset 70]

0x7E

(126)

1 to 0x10

(16)

0x1A (26)

- - - -

26026

float

RWES

[`dio]
[`Set]
Digital Input/Output Menu

[`dir]
[ dir]

Digital Input/Output (1

to 12)

Direction

Set this function to operate

as an input or output.

[OtPt]

Output (68)

[``in]

Input Voltage (193)

[iCon]

Input Dry Contact

(44)

Output

1820

[offset 30]

0x6A

(106)

1 to 0x0C

(12)

1

38

6001

uint

RWES

Note: Some values will be rounded off to fit in the four-character display .