Ez zone series rm, Declaration of conformity, Watlow – Watlow EZ-ZONE RM-Scanner-Modul User Manual
Page 139: Iso 9001
Watlow EZ-ZONE
®
RMS Module
•
136
•
Appendix
Declaration of Conformity
CE DOC EZ-ZONE RM-09-13
Page 1 of 1
EZ Zone Series RM
WATLOW
an
ISO 9001
approved facility since 1996.
1241 Bundy Blvd.
Winona, MN 55987 USA
Declares that the following Series RM (Rail Mount) products:
Model Numbers:
RM followed by additional letters or numbers describing use of up to four module
options of various inputs and outputs or communications.
Classification:
Temperature control, Installation Category II, Pollution degree 2
Voltage and Frequency:
SELV 24 to 28 V
ac 50/60 Hz or dc
Power Consumption:
RMA models 4 Watts, any other RM model 7 Watts
Environmental Rating:
IP20
Meet the essential requirements of the following European Union Directives by using the relevant standards show
below to indicate compliance.
2004/108/EC Electromagnetic Compatibility Directive
EN 61326-1
2006
Electrical equipment for measurement, control and laboratory use – EMC
requirements, Industrial Immunity, Class A Emissions (Not for use in a
Class B environment without additional filtering).
EN 61000-4-2
2008
Electrostatic Discharge Immunity
EN 61000-4-3
2010
Radiated Field Immunity
EN 61000-4-4
2011
Electrical Fast-Transient / Burst Immunity
EN 61000-4-5
2006
Surge Immunity
EN 61000-4-6
2008
Conducted Immunity
EN 61000-4-11
2004
Voltage Dips, Short Interruptions and Voltage Variations Immunity
EN 61000-3-2
2005
Harmonic Current Emissions
EN 61000-3-3
1
2005
Voltage Fluctuations and Flicker
SEMI F47
2000
Specification for Semiconductor Sag Immunity Figure R1-1
1
NOTE: To comply with flicker requirements cycle time may need to be up to 160 seconds if load current
is at 15A, or the maximum source impedance needs to be < 0.13Ω
Ω
Ω
Ω. Control power input of RM models
comply with 61000-3-3 requirements.
2006/95/EC Low-Voltage Directive
EN 61010-1
2010
Safety Requirements of electrical equipment for measurement, control and
laboratory use. Part 1: General requirements
Compliant with 2002/95/EC RoHS Directive
Per 2002/96/EC W.E.E.E Directive
Please Recycle Properly
Joe Millanes
Winona, Minnesota, USA
Name of Authorized Representative
Place of Issue
Director of Operations
September 2013
Title of Authorized Representative
Date of Issue
Signature of Authorized Representative