Chapter 3 Operations Page

RM Scanner Module

Operations Page

Display

Parameter Name

Description

Range

Default

Modbus

Relative

Address

CIP

Class

Instance

Attribute

hex (dec)

Profibus

Index

Parameter

ID

Data

Type

& Read/

Write

[`ACt]
[oPEr]
Action Menu

[`Ei;S]
[ Ei.S]

Action (1 to 16)

Event Input Status

View this input state.

[`off]

Off (62)

[``on]

On (63)

2188
[offset 20]

0x6E (110)

1 to 0x10

(16)

5

81

10005

uint
R

No Dis-

play

Function Key (1)

Function Key State

View current state of func-

tion key 1.

Off (62)
On (63)

- - - -

- - - -

- - - -

- - - -

3024

uint

R

No Dis-

play

Function Key (2)

Function Key State

View current state of func-

tion key 2.

Off (62)
On (63)

- - - -

- - - -

- - - -

- - - -

3030

uint

R

[ALM]
[oPEr]
Alarm Menu

[`A;Lo]
[ A.Lo]

Alarm (1 to 16)

Low Set Point

If Alarm Type (Setup

Page, Alarm Menu) is

set to:

process - set the process

value that will trigger a

low alarm.

-1,999.000 to 9,999.000°F

or units

-1,128.000 to 5,537.000°C

32.0 °F

or

units

0.0°C

2502
[offset 60]

0x6D

(109)

1 to 0x10

(16)

2

18

9002

float
RWES

[`A;hi]
[ A.hi]

Alarm (1 to 16)

High Set Point

If Alarm Type (Setup

Page, Alarm Menu) is

set to:

process - set the process

value that will trigger a

high alarm.

-1,999.000 to 9,999.000°F

or units

-1,128.000 to 5,537.000°C

300.0°F

or

units

150.0°C

2500
[offset 60]

0x6D

(109)

1 to 0x10

(16)

1

19

9001

float
RWES

[A;Clr]
[ A.hi]

Alarm (1 to 16)

Clear Request

User interface (RUI) ac-

cess to clear an alarm

Clear (129)

Ignore (204)

Ignore

- - - -

- - - -

- - - -

9026

uint

RW

[A;sir]
[A.Sir]

Alarm (1 to 16)

Silence Request

User interface (RUI) ac-

cess to silence an alarm

Ignore (204)
Silence (108)

Ignore

- - - -

- - - -

- - - -

9027

uint

RW

[`A;st]
[ A.St]

Alarm (1 to 16)

State

View state of alarm

Startup (88)
None (61)
Blocked (12)
Alarm low (8)
Alarm high (7)
Error (28)

Startup

2516
[offset 60]

0x6D

(109)

1 to 0x10

(16)

9

- - - -

9009

uint

R

No Dis-

play

Alarm (1 to 16)

Latched

Read this register to de-

termine if the alarm is

latched

No (59)
Yes (106)

No

2518
[offset 60]

0x6D

(109)

1 to 0x10

(16)

0x0A (10)

- - - -

9010

uint

R

Note: Some values will be rounded off to fit in the four-character display . Full values
can be read with other interfaces .

If there is only one instance of a menu, no submenus will appear .

R: Read

W: Write

E: EEPROM

S: User Set