Watlow EZ-ZONE RM-Scanner-Modul User Manual
Page 76
Watlow EZ-ZONE
®
RMS Module
•
73
•
Chapter 4 Setup Page
RM Scanner Module
•
Setup Page
Display
Parameter Name
Description
Range
Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Parameter
ID
Data
Type
&
Read/
Write
[SFn;g]
[SFn.g]
Logic (1 to 24)
Source Function G
Set the type of function
that will be used for this
source.
[[nonE]
None (61)
[ALM]
Alarm (6)
[`CPE]
Compare (230)
[`Ctr]
Counter (231)
[`dio]
Digital I/O (1142)
[Ent;A]
Profile Event Out A
(233)
[Ent;b]
Profile Event Out B
(234)
[Ent;C]
Profile Event Out C
(235)
[Ent;d]
Profile Event Out D
(236)
[Ent;E]
Profile Event Out E
(247)
[Ent;F]
Profile Event Out F
(248)
[Ent;g]
Profile Event Out G
(249)
[Ent;h]
Profile Event Out H
(250)
[`FUn]
Function Key (1001)
[lim]
Limit (126)
[`lgC]
Logic (239)
[SoF;1]
Special Function Out-
put 1 (1532)
[SoF;2]
Special Function Out-
put 2 (1533)
[SoF;3]
Special Function Out-
put 3 (1534)
[SoF;4]
Special Function Out-
put 4 (1535)
[tMr]
Timer (244)
[`uAr]
Variable (245))
None
6312
[offset 80]
0x7F (127)
1 to 0x18
(24)
7
- - - -
27007
uint
RWES
[`Si;g]
[ Si.g]
Logic (1 to 24)
Source Instance G
Set the instance of the
function selected above.
1 to 250
1
6328
[offset 80]
0x7F (127)
1 to 0x18
(24)
0xF (15)
- - - -
27015
uint
RWES
[`S2;g]
[ SZ.g]
Logic (1 to 24)
Source Zone G
Set the zone of the function
selected above.
0 to 16
0
6344
[offset 80]
0x7F (127)
1 to 0x18
(24)
0x17 (23)
- - - -
27023
uint
RWES
Note: Some values will be rounded off to fit in the four-character display .
Full values can be read with other interfaces .
If there is only one instance of a menu, no submenus will appear .
R: Read
W: Write
E:
EEPROM
S:
User
Set