List of ASEL, PSEL and SSEL network I/O parameters
No. Parameter
name
Factory
setting
Input range
Remarks
1
I/O port assignment type
0
0~20
0: Fixed assignment
1: Automatic assignment
14
Network I/F module – Number of
available remote input ports
64
0~256
Multiple of 8
15
Network I/F module – Number of
available remote output ports
64
0~256
Multiple of 8
16
Network I/F module – First input
port number based on mount
assignment
0 -1~599
0 + (multiple of 8) (Invalid, if a value is
entered with a negative sign.)
17
Network I/F module – First output
port number based on mount
assignment
300 -1~599
300 + (multiple of 8) (Invalid, if a value is
entered with a negative sign.)
18
Network I/F module – Error
monitor
1 0~5
0: Do not monitor
1: Monitor
* If a network link error status has
continued for at least the network-link
error check timer value, a system error
will occur. (Refer to I/O parameter No.
120.)
* Some exceptions apply.
120 Network attribute 1
1H
0H~
FFFFFFFFH
Bits 0 to 3: Reserved by the system.
Bits 4 to 11: Network-link error check
timer value (Setting unit: 10 msec)
This parameter is valid only when I/O
parameter No. 18 is set to “1.”
(Example) If the set value (bits 4 to 11)
is “05H,” the timer period
becomes 10 ms x 5 = 50 ms.
If the set value is “0H,” a
system error will occur
immediately upon occurrence
of a network link error.
225 Network I/F module control
2H
Read only
Bits 0 to 3: Network I/F module type
(0: Not installed, 1: CC-Link module, 2:
DeviceNet module)
226
Network I/F module –
Communication attribute 1
0 0~999
Node address of the network I/F module
* DeviceNet module: 0 to 63
227
Network I/F module –
Communication attribute 2
0H
0H~
FFFFFFFFH
Bits 0 to 3: Baud rate type of the network
I/F module
* With the DeviceNet module, the baud
rate is automatically set to the same
value as the baud rate set in the
master. Accordingly, you need not set
the baud rate.