beautypg.com

IAI America E-Con User Manual

Page 94

background image

86

7.

ASEL, PSEL

and SSEL

List of ASEL, PSEL and SSEL network I/O parameters

No. Parameter

name

Factory

setting

Input range

Remarks

1

I/O port assignment type

0

0~20

0: Fixed assignment
1: Automatic assignment

14

Network I/F module – Number of
available remote input ports

64

0~256

Multiple of 8

15

Network I/F module – Number of
available remote output ports

64

0~256

Multiple of 8

16

Network I/F module – First input
port number based on mount
assignment

0 -1~599

0 + (multiple of 8) (Invalid, if a value is
entered with a negative sign.)

17

Network I/F module – First output
port number based on mount
assignment

300 -1~599

300 + (multiple of 8) (Invalid, if a value is
entered with a negative sign.)

18

Network I/F module – Error
monitor

1 0~5

0: Do not monitor
1: Monitor
* If a network link error status has

continued for at least the network-link
error check timer value, a system error
will occur. (Refer to I/O parameter No.
120.)

* Some exceptions apply.

120 Network attribute 1

1H

0H~

FFFFFFFFH

Bits 0 to 3: Reserved by the system.
Bits 4 to 11: Network-link error check
timer value (Setting unit: 10 msec)
This parameter is valid only when I/O
parameter No. 18 is set to “1.”
(Example) If the set value (bits 4 to 11)

is “05H,” the timer period
becomes 10 ms x 5 = 50 ms.
If the set value is “0H,” a
system error will occur
immediately upon occurrence
of a network link error.

225 Network I/F module control

2H

Read only

Bits 0 to 3: Network I/F module type
(0: Not installed, 1: CC-Link module, 2:
DeviceNet module)

226

Network I/F module –
Communication attribute 1

0 0~999

Node address of the network I/F module
* DeviceNet module: 0 to 63

227

Network I/F module –
Communication attribute 2

0H

0H~

FFFFFFFFH

Bits 0 to 3: Baud rate type of the network
I/F module
* With the DeviceNet module, the baud

rate is automatically set to the same
value as the baud rate set in the
master. Accordingly, you need not set
the baud rate.

This manual is related to the following products: