2 interface specifications – IAI America E-Con User Manual
Page 72
64
5. RCS-C and E-Con
4.2 Interface
Specifications
Item Specification
DeviceNet 2.0 (*1)
Group 2 only server
Communication protocol
Network-powered insulation node
Bit strobe
Support connection
Master-slave connection
Polling
Baud rate
500 k / 250 k / 125 kbps (selectable by DIP switches)
Baud rate
Maximum network length
Maximum branch
line length
Total branch
line length
500 kbps
100 m
39 m
250 kbps
250 m
78 m
125 kbps
500 m
6 m
156 m
Communication cable length
Note) When a large-size DeviceNet cable is used.
Communication power supply
24 VDC (supplied from DeviceNet)
Consumption current of
communication power supply
60 mA
Number of occupied nodes
1 node
Connector
MSTBA2.5/5-G-5.08AU M (*2) by Phoenix Contact
(*1) RCS-C controllers are already certified (test version 15).
Certification is pending for E-Con controllers.
(*2) The cable-end connector is a standard accessory.
SMSTB2.5/5-ST-5.08AU by Phoenix Contact
5.2