3. XSEL-R/S/RX/SX/RXD/SXD
(3) Example for when using DeviceNet and I/O Board 1 together
It is how to establish the setting when using DeviceNet to 192 points of each input and output from the top
of the extended I/O ports and assigning the I/O board (48 points for each input and output) to the standard
I/O ports.
Standard Input Ports No.0 to 191
Standard Output Ports No.300 to 491
(DeviceNet board)
Standard Input Port No.192 to 239
Standard Output Port No.492 to 539
(I/O board)
• I/O Parameters
No.
Parameter name
Default
(Reference)
Input Range
Unit
Remarks
1
I/O Port Allocation Type
1
0 to 1
0
0:Fixed Allocation
1:Automatic Allocation
•Reference 1 Priority of I/O Port Assignment
when automatically assigned
Port Number
(No.0 to 299/No.300 to 599)
1) Network I/F Module 1
2) I/O slot 1 (I/O1) Mounting board
3) I/O slot 2 (I/O2) Mounting board
* I/O slot 1 (I/O1) Assigned for the
continuously mounted range from
mounting board
•Reference 2 Priority of extension I/O ports at
automatic assignment
Port Number
(No.1000 to 3999/No.4000 to 6999)
1) Network I/F Module 2
2) Expansion I/O unit
3) IA Net
2
Standard I/O Fix-Allocated
Input Port Start No.
0
-1 to 599
192
0+ (Multiples of 8)
[Ineffective when -1 is selected]
3
Standard I/O Fix-Allocated
Output Port Start No.
300
-1 to 599
492
300+ (Multiples of 8)
[Ineffective when -1 is selected]