3. XSEL-R/S/RX/SX/RXD/SXD

[3] DeviceNet Board Use Setting

Set “1” (Monitoring: use DeviceNet board) to I/O Parameter No.235.

No.

Parameter name

Default

(Reference)

Input Range

Unit

Remarks

235

Network I/F Module 2
Error Monitoring

1

0 to 5

0:No Monitoring (Not to monitor

condition of link to PLC (master))

1:Monitoring

[4] Node address setting

Set the node address to I/O Parameter No. 237

No.

Parameter name

Default

(Reference)

Input Range

Unit

Remarks

237

Network I/F Module 2
Node Address

0

0 to 63

DeviceNet node address range:

0 to 63

Note If a number out of the settable range is selected, “D75: Fieldbus Parameter Error” will occur.

[5] Baud Rate Setting

Set the communication speed in I/O Parameter No. 238. Match the setting to the communication speed of
the master unit.

No.

Parameter name

Default

(Reference)

Input Range

Unit

Remarks

238

Network I/F Module 2
Baud Rate

0

0 to 2

0: 125Kbps
1: 250Kbps
2: 500Kbps

Note If a number out of the settable range is selected, “D75: Fieldbus Parameter Error” will occur.

[6] Number of I/O Port Setting

Set the number of ports to be used for I/O Parameters No. 231 to 232.
Note Set a number that is a multiple of 8.

No.

Parameter name

Default

(Reference)

Input Range

Unit

Remarks

231

No. of Network I/F
Module 2 Remote
Input Ports

0

0 to 256

8 port unit

232

No. of Network I/F
Module 2 Remote
Output Ports

0

0 to 256

8 port unit