PAGE 4 - 19
Chapter 4: Installation & Wiring
4.7.5 External DIP Switch
¦
¦
¦
¦
(Located on bottom of unit)
DIP SWITCH (Factory Setting)
(Bottom View)
4.8 Setting Default TCP/IP Address
¦
¦
¦
¦
User Console Ethernet Port
For Multi-2 units with firmware 1.16 or greater, the IP address for the User Console Ethernet Port can be
reset to the default setting by following the directions below.
1. Turn off power to the unit
2. Turn “ON” DIP Switch no. 1, 2 & 4
3. Depress and HOLD the RESET button (on front of unit) and turn the power back on
4. Hold the RESET button until the green ACC LED turns on solid
5. Turn power off and reset DIP Switch back to original setting
When power is reapplied, the TCP/IP settings will revert to the following default;
IP Address
: 192.168.10.10
Subnet Mask
: 255.255.255.0
Default Gateway
: 192.168.10.1
4.9 Firmware Flash Connector
Upgrades or revisions to firmware are handled easily with the on board Flash Connector located on
the bottom of each Multi-2 Unit. There is no need to remove or disassemble the unit. A flash adapter
(CONTROLLER-ROM) containing the new firmware can be connected to connector CN8 with the
power off to the unit. The power is then cycled on until the ACCEPT LED is blinking indicating the
firmware upload is complete. Turn off power and remove the flash adapter. The firmware update is
now complete.
Note: This connector is for FEC use only and it is not recommended for use other than FEC.
No.
OFF
ON
4
Not Used
3
Not Used
2
Angle resolution: 0.1 Angle resolution: 1
1
EXT. I/O ENABLE EXT. I/O DISABLE
FRONT
Switch 1: I/O Enable / Disable Test Mode
If Switch No.1 is turned ON, the Input / Output Module
will be bypassed and the STOP signal will be enabled
allowing Manual operations through the front panel
buttons for testing purposes. This is particularly
useful when Fieldbus interfaces are installed and
connection to the master device is not possible.
When finished testing the equipment, be sure to
turn Switch No. 1 OFF.
Do not change Switch No. 3 or 4.
Switch 2 : Angle Resolution
Normal angle resolution is 1.0 degree. Angle
resolution of 0.1 degree is available using this switch.
Note: SAN unit firmware version 3.3x is required and
the function enabled if using the AFC User Console for
monitoring purposes.
Firmware Flash Connector (CN8)