MOD 30ML Operation
APPENDIX A - EVENT CODES
A-6
Table A-2. Event Codes, Description and Action
Block
Type Codes
Full Message Text
Description/Action
IF
4
DEFAULT DATABASE CHECKSUM
ERROR
The instrument was shut down due to a
checksum error in the default database.
IF
5
MAIN DATABASE CHECKSUM ERROR
The instrument was shut down due to a
checksum error in the main database.
IF
6
INSTRUMENT IS UNCONFIGURED
There is no valid user database in the
instruments main RAM.
IF
7
MAIN DATABASE VERSION ERROR
A user database was rejected because the
instrument does not have the hardware and/or
firmware resources to run it.
IF
8
MEMORY MODULE CHECKSUM ERROR The memory module database has been
marked bad because a checksum error was
found in it.
IF
9
MEMORY MODULE IS UNCONFIGURED A memory module database was not
downloaded because no valid database was
found in the module.
IF
10
MEMORY MODULE DATABASE
VERSION ERROR
A memory module database was not
downloaded because the instrument does not
have the hardware and/or firmware resources
to run it.
IF
11
MEMORY MODULE IS WRITE
PROTECTED
The switch on the module is in the ‘read only’
position.
IF
12
MEMORY MODULE IS SOFT WRITE
PROTECTED
The write protect bit in the module RAM has
been set by software.
IF
13
INSTRUMENT IS OVERCONFIGURED
The instrument is unable to complete all of its
tasks at the intervals specified. The scan
execution times should be examined to
determine which tasks should be simplified or
run at a slower rate or items should be moved
to another task. Note that when the instrument
is overconfigured, all tasks run at a
proportionally slower rate. This may be a
temporary condition if the instrument is getting
too many messages. You should not ignore
this condition if it is persistent.
IF
14
INSTRUMENT POWERED UP
The instrument went through power-up. A time
stamp indicating the time power was restored is
entered in the event queue.
IF
15
INSTRUMENT POWERED DOWN
The instrument lost power. A time stamp
indicating the time power was lost is entered in
the event queue.