MOD 30ML Operation
SETUP
2-12
Table 7. System Template Configuration (Cont’d)
Step
Step Description
Line 1
Line 2
Line 6
Entry Description
7C
System Passwords (Entry)
∇ moves down to Step 7C1
NXT, PRV change step
SYSTEM PASWORDS
The passwords set here will restrict
access to tuning and configuration
features.
7C1
Tune Passwords
∇ ∆ changes number, ENT enters
NXT, PRV change step
TUNE PASSWORD
0
Enter a number required to access
tuning parameters.
7C2
Configure Passwords
∇ ∆ changes number, ENT enters
NXT, PRV change step
CONFIG PASSWORD
0
Enter a number required to access
configuration parameters.
7C3
Access Timeout
∇ ∆ changes number, ENT enters
NXT, PRV change step
ACCESS TIMEOUT
0
0-54 minutes; 0=infinite
The time in minutes that the tune
and configure access levels will
timeout and return to the operate
level after last keyboard activity.
7C4
System (Passwords Exit)
∆ moves up to Step 7C
NXT, PRV change step
SYSTEM
7D
System Alarms (Entry)
∇ moves down to Step 7D1
NXT, PRV change step
SYSTEM ALARMS
Alarm indication rates apply to
light, display and beeper. Alarms
are: unacknowledged diagnostics,
high or low process and deviation
conditions, and input quality.
7D1
Diagnostic Flash/Beep Rate
∇ ∆ change value, ENT enters
NXT, PRV change step
DIAGNSTC RATE FAST
FAST = off 100msec, on 300 msec
SLOW = off 250msec, on 750msec
7D2
Diagnostic Flash
∇ ∆ change value, ENT enters
NXT, PRV change step
DIAGNSTC FLASH OFF
OFF = flashing is disabled
ENABLE = flash display (LED
always flashes for diagnostic)
7D3
Diagnostic Beep
∇ ∆ change value
DIAGNSTC BEEP ENABLE
OFF = beeping is disabled
ENABLE = beep for diagnostic
7D4
Minimum Low Alarm Priority
∇ ∆ change value, ENT enters
NXT, PRV change step
MINIMUM LOW
PRI
100
All process alarms with priority >=
this value (2 - 255) are considered
LOW priority for display purposes.
7D5
High Priority Process Alarm Flash/
Beep Rate
∇ ∆ change value, ENT enters
NXT, PRV change step
HIGH PRI RATE
FAST
FAST = off 100msec, on 300 msec
SLOW = off 250msec, on 750msec
7D6
High Priority Process Alarm Flash
∇ ∆ change value, ENT enters
NXT, PRV change step
HIGH PRI FLASH
OFF
OFF = flashing is disabled
ENABLE = flash display on alarm
7D7
High Priority Process Alarm Beep
∇ ∆ change value, ENT enters
NXT, PRV change step
HIGH PRI BEEP
OFF
OFF = beeping is disabled
ENABLE = beep on alarm
7D8
Low Priority Process Alarm Flash/
Beep Rate
∇ ∆ change value, ENT enters
NXT, PRV change step
LOW PRI RATE
SLOW
FAST = off 100msec, on 300 msec
SLOW = off 250msec, on 750msec
7D9
Low Priority Process Alarm Flash
∇ ∆ change value, ENT enters
NXT, PRV change step
LOW PRI FLASH
OFF
OFF = flashing is disabled
ENABLE = flash display on alarm