MOD 30ML Multiloop Controller
OPERATION
3-11
3.9.2
Single Loop Automatic Operation with Remote Set-Point
When a control loop is configured for single loop operation with remote set-point, the front
panel displays and control key operations resemble the examples below.
[AUT] indicates that the controller is in automatic.
[LOC] indicates local set-point. The R/L key is used to
switch to remote set-point.
[SP] indicates that the current local set-point value is
displayed on Line 6 (bottom line). An engineering units
label has been configured for the value.
∇/∆ arrow display indicates that the local set-point can
be changed in automatic.
Press the scroll key to display the remote set-point
ratio (RA appears on line 5 and the ratio value on line
6), press the scroll key again to display the remote set-
point bias (BI appears on line 5 and the bias value on
line 6) and press the scroll key again to display the
remote set-point.
[RSP] on Line 5 indicates that Line 6 is showing the
remote set-point value (before ratio and bias are
applied).
Press the R/L key to switch to remote set-point.
[REM] appears on Line 4 indicating that the active set-
point is from a remote source.
∇/∆ arrow display disappears because remote set-
point cannot be changed.
Press the scroll key until you get [SP] on Line 5. Line 6
now shows the remote set-point value (with ratio and
bias applied). The
∇/∆ arrow display remains blank
because remote set-point is not adjustable from the
front panel.