MOD 30ML Multiloop Controller

OPERATION

3-28


5. Tune the configured control parameters using the front panel keys as shown in the

illustration. The parameters available for tuning are as follows:

• Parameters which are always available:

Action [ACTION], Gain [GAIN], Reset [RESET], Preact [PREACT], Set-Point Low
Limit [SP LOLIM], set-point high limit [SP HILIM], output low limit [OP LOLIM],
output high limit [OP HILIM].

• Parameters which are available only when configured:

Filter type [FIL TYP], Filter Time [FIL TIME], Feed Forward Gain [FF GAIN], Feed
Forward Bias [FF BIAS], and Manual Reset [MAN RSET]. Prior to the
appearance of the feed forward gain and bias parameters, the Feed Forward
Type [FF TYPE] is identified on Line 6 as [MULT] or [ADD] for information only; it
is not tunable.


6. When the [EXIT] [TUNING] prompt appears after the last tuning display, proceed as

follows:

• Press the R/L[PRV] key to return to the previous display.
• Press the Scroll[NXT] key to return to the start of the tuning sequence.
• Press the Up [∆] key to return to the runtime displays.