MOD 30ML Operation
SETUP
2-20
Table 8. User Compound Template Configuration (Cont’d)
Step
Step Description
Line 1
Line 2
Line 6
Entry Description
8G
Output (Entry)
∇ moves down to Step 8G1
NXT, PRV change step
CTAG01 OUTPUT
8G1
Output Slot Position
∇ ∆ change value, ENT enters
NXT, PRV change step
OUTPUT
SLOT
OUT CH 1
NONE, OUT CH 1, OUT CH 2,
S01 to S11. Only available outputs
are listed.
8G2
Output Low Signal
∇ ∆ change value, ENT enters
NXT, PRV change step
OUTPUT
LO SIGNL 4.0
0% of the output range.
8G3
Output High Signal
∇ ∆ change value, ENT enters
NXT, PRV change step
OUTPUT
HI SIGNL 20.0
100% of the output range.
8G4
Output Display Format
∇ ∆ change value, ENT enters
NXT, PRV change step
OUTPUT
DISP FMT FLOAT 3
Float 0 = x, Float 1 = x.x
Float 2 = x.xx and so forth to
Float 6 = x.xxxxxx
8G5
Output Low Limit
∇ ∆ change value, ENT enters
NXT, PRV change step
OUTPUT
LO LIMIT -10.0
PID output limited to this number or
above.
8G6
Output High Limit
∇ ∆ change value, ENT enters
NXT, PRV change step
OUTPUT
HI LIMIT 110.0
PID output limited to this number or
below.
8G7
Output Restart Type
∇ ∆ change value, ENT enters
NXT, PRV change step
RESTART TYPE
PREVIOUS
PREVIOUS, PRESET
8G8
Output Initial Value
∇ ∆ change value, ENT enters
NXT, PRV change step
OUTPUT
INIT VAL 0.0
8G9
Output (Exit)
∆ moves up to Step 8G
NXT, PRV change step
COMPOUND
8H
Alarms (Entry)
∇ moves down to Step 8H1
NXT, PRV change step
CTAG01 ALARMS
8H1
Process Value Alarms
PV ALARMS
8H1A
Process Value Alarm 1 Type
∇ ∆ change value, ENT enters
NXT, PRV change step
NXT goes to Alarm 2 from NONE
PV ALM 1 TYPE
NONE
NONE,
HIGHHIGH (>=), HIGH (>=),
LO (<=), LOW LOW (<=).
8H1A1 Process Value Alarm 1 Trip Value
PV ALM 1 TRIP VAL 0.000
Value where input will cause alarm
to trip.
8H1A2 Process Value Alarm 1 Hysteresis
PV ALM 1 HYSTRSIS 2.000
Absolute offset to clear alarm.
8H1A3 Process Value Alarm 1 Priority
PV ALM 1 PRIORITY 1
0 to 255. 0 = suppress unack.
8H1A4 Process Value Alarm 1 Digital Output PV ALM 1 DIG OUT NONE
NONE, S01 through S11
8H1B
Process Value Alarm 2 Type
Same as Alarm 1
PV ALM 2 TYPE
NONE
NONE, HIGHHIGH, HIGH, LOW,
LOW LOW
8H1C
Process Value Alarm 3 Type
Same as Alarm 1
PV ALM 3 TYPE
NONE
NONE, HIGHHIGH, HIGH, LOW,
LOW LOW
8H1D
Process Value Alarm 4 Type
Same as Alarm 1
PV ALM 4 TYPE
NONE
NONE, HIGHHIGH, HIGH, LOW,
LOW LOW
8H1E
Process Value Alarms (Exit)
∆ moves up to Step 8H1
NXT, PRV change step
ALARMS