MOD 30ML Multiloop Controller
OPERATION
3-21
Input Variable Alarm Display
[PV] indicates that this display applies to the process
input variable.
[HI] indicates that the alarm is activated by increasing
input.
[UAK] indicates that the alarm is active and has not
been acknowledged.
Press the ‘A' key to acknowledge the alarm:
If alarm is still active [ACT] appears .
If alarm is no longer active [CLR] appears, and this
display is deleted upon exit.
[RET] indicates that the R/L key can be pressed to
return to the runtime displays.
Intensified segment indicates alarm trip point.
Current value of process variable is above the trip
point. Alarm remains active [ACT] after
acknowledgement.
Control Output Alarm Display
[OUT] indicates that this display applies to the control
output.
[LO] indicates that the alarm is activated by
decreasing output.
[UAK] indicates that the alarm is active and has not
been acknowledged. Press the ‘A' key to
acknowledge the alarm. If alarm is still active [ACT]
appears . If alarm is no longer active [CLR] appears,
and this display is deleted upon exit.
[RET] indicates that the R/L key can be pressed to
return to the runtime displays.
Intensified segment indicates alarm trip point.
Current output value is below the trip point. Alarm
is active [ACT] after acknowledgement.