Micromod MOD: 30ML Operation and Template Setup User Manual
Page 27
MOD 30ML Operation
SETUP
2-17
Table 8. User Compound Template Configuration (Cont’d)
Step
Step Description
Line 1
Line 2
Line 6
Entry Description
Steps 8E3A through F only presented when there is a remote setpoint input
8E3A
Local Setpoint Enable
∇ ∆ change value, ENT enters
NXT, PRV change step
LOCAL SETPOINT ENABLE
Enable or Disable a local setpoint
value
8E3B
Setpoint Ratio
∇ ∆ change value, ENT enters
NXT, PRV change step
SETPOINT RATIO DISABLE
Enable or Disable a remote
setpoint ratio value
8E3C
Setpoint Ratio Value
∇ ∆ change value, ENT enters
NXT, PRV change step
SETPOINT RATIO
1.000
Initial ratio value.
Auto balance calculation is:
(Active Setpoint - Bias) / Rem SP
8E3D
Setpoint Bias
∇ ∆ change value, ENT enters
NXT, PRV change step
SETPOINT BIAS DISABLE
Enable or Disable a remote
setpoint bias value
8E3E
Setpoint Bias Value
∇ ∆ change value, ENT enters
NXT, PRV change step
SETPOINT BIAS
0.000
Initial bias value.
Auto balance calculation is:
Active Setpoint - (Rem SP * Ratio)
8E3F
Setpoint Balance
∇ ∆ change value, ENT enters
NXT, PRV change step
SETPOINT BALANCE AUTO
RAT
AUTO RAT, Ratio value calculated
to balance transition to remote.
STANDARD, Ratio and Bias use
the operator values.
AUTO BIA, Bias value calculated to
balance transition to remote.
Setpoint (Cont’d)
8E4
Setpoint Low Limit
∇ ∆ change value, ENT enters
NXT, PRV change step
SETPOINT LO LIMIT 0.000
Setpoint values to the PID
algorithm are limited to this number
or above.
8E5
Setpoint High Limit
∇ ∆ change value, ENT enters
NXT, PRV change step
SETPOINT HI LIMIT 100.000
Setpoint values to the PID
algorithm are limited to this number
or below.
8E6
Setpoint Restart Mode
∇ ∆ change value, ENT enters
NXT, PRV change step
RESTART SP
MODE PREVIOUS
Previous (requires setting initial SP
Mode), Local or Remote
Local only for Master Controller.
8E7
Setpoint Initial Mode
∇ ∆ change value, ENT enters
NXT, PRV change step
INITIAL SP
MODE LOCAL
Local or Remote
Local only for Master Controller.
8E8
Setpoint Restart Value
∇ ∆ change value, ENT enters
NXT, PRV change step
RESTART SP
VAL PREVIOUS
Previous (enter an Initial Value) or
Preset (enter a Restart Value).
8E9
Setpoint Restart Preset Value
∇ ∆ change value, ENT enters
NXT, PRV change step
RESTART VALUE
0.0
Enter restart value for setpoint.
8E10
Setpoint Initial Value
∇ ∆ change value, ENT enters
NXT, PRV change step
INITIAL VALUE
0.0
Enter initial value for setpoint.
8E11
Setpoint Tracking
∇ ∆ change value, ENT enters
NXT, PRV change step
SETPOINT TRACK DISABLE
Enable or Disable
When active, setpoint tracks input
while in manual.
8E12
Setpoint (Exit)
∆ moves up to Step 8E
NXT, PRV change step
COMPOUND