MOD 30ML Multiloop Controller
OPERATION
3-26
3.14.2 Alarm Parameters
The alarm tuning sequence is accessed from the runtime display. Enter the tuning sequence
and make tuning adjustments as follows:
1. Press the Scroll key repeatedly until [TUNE???] appears on Line 6.
2. Press the Down (
∇) key. [ALARM] appears on Line 6 and [ENT] flashes next to the Scroll
key.
3. Press the Scroll key to start the tuning sequence.
• If a tune password is not required, an alarm tuning display appears; go to step 4.
• If a tune password is required, [TUNE] and [PASSWORD] appear on Lines 1 and
2. Use the Up(
∆) key to enter the password number, then press scroll while
[ENT] is flashing to access the tune sequence. An alarm tuning display appears.
4. Tune the configured alarms using the front panel keys as shown below. Configured
alarms can be on the process variable[PV], set-point/process deviation[DEV], and output
[OP]. The alarm type for each configured alarm can be high[H], high high[HH], low[L], or
low low[LL]. The tunable alarm parameters are: Trip value[TRIP VAL], hysteresis[HYST],
priority[PRIORITY], and suppression[SUPPRESS] or [ENABLE].
5. When the [EXIT] [TUNING] prompt appears after the last tuning display, proceed as
follows:
• Press the R/L[PRV] key to return to the previous display.
• Press the Scroll[NXT] key to return to the start of the tuning sequence.
• Press the Up [∆] key to return to runtime
Alarm Input
Alarm Type
Press to return to runtime display.
Press to return to previous display.
From [NXT], press to advance to next display.
From flashing [ENT], press to enter displayed
parameter. value.
∇ ∆ adjust parameter value or select
suppress/enable