Figure 104: jumper settings without remote panel, Figure 105: jumper settings with remote panel, Figure 106: internal controller voltages – MaxPower Corp Gamatronic Power+ M50-RM User Manual
Page 95: Figure 107: battery parameters
Gamatronic Electronic Industries Ltd.
POWER+ RM
50
K
VA, N.Am. Std. – User Guide, Release 1.9
79
6.
View the system jumper settings without remote panel:
[Main Menu > SYSTEM >
▼ ▼ ▼]
JMP: JMP1, JMP2, JMP3, JMP6 and JMP9
=IN 1. NOT HARD SILICON
2. SILICON MODE 6. NO RMT PAN.
12369 3. CAPACITY LOW 9. AC: 120V
Figure 104: Jumper settings WITHOUT remote panel
7.
View the system jumper settings with remote panel:
[Main Menu > SYSTEM >
▼ ▼ ▼]
JMP: JMP1, JMP2, JMP3, JMP6 and JMP9
=IN 1. NOT HARD SILICON
2. SILICON MODE 6. Remote pan.
12369 3. CAPACITY LOW 9. AC: 120V
Figure 105: Jumper settings WITH remote panel
Note: In Figure 104 and Figure 105, “Silicon mode” indicates that the configuration jumper is
installed, thus allowing for modifications. “Hard Silicon” indicates that the factory defaults
hard reset jumper is installed. This is required only at the factory or whenever software
reset fails. Refer to section 8.15.9.3 for a detailed description of jumpers.
8.
View the internal controller voltages:
[Main Menu > SYSTEM >
▼ ▼ ▼ ▼]
5VDC : 5.19V CONTROLLER INTERNAL
12VDC: 12.01V VOLTAGES
5VP : GOOD
5V2 : GOOD -12VDC: GOOD
Figure 106: Internal controller voltages
9.
View battery parameters:
[Main Menu > SYSTEM >
▼ ▼ ▼ ▼ ▼]
BATTERY CHARGE LEVEL: 010Ah 050%
WHILE TOTAL CAPACITY: 020Ah
REMAINING BACKUP: 0010 MINUTES
BATTERY TEMPERATURE: 12°C