VA, N.Am. Std. – User Guide, Release 1.9

160

9.3.7.6

Shutdown Targets

The “Shutdown Targets” option of the Configuration menu is where you record the IP address of
the computers that you want to have an orderly shutdown performed in the event of an ac mains
power outage.

To use this option, the computer in question must have a Shutdown Agent installed on it. The
Shutdown Agent is available as a self-installing “setup.exe” file intended to be run on the target
computer. The install file can be downloaded from the Internet by clicking on the “Shutdown
Agent” link in the bottom right of the screen as shown in Figure 317.

Note: The built-in Web interface supports a maximum of 15 shutdown targets. Customers

requiring a larger number of shutdown targets should inquire about the PSM-AC for
Power+ software product (see section 10 on page 164).

Figure 317: Define computers for auto-shutdown

Table 20: Defining computers for auto-shutdown

F

IELD

D

ESCRIPTION

Address

IP address of the computer to be automatically shut down in the event of
a power failure.

Ac Fail delay
(minutes)

Delay in minutes between ac failure and initiation of the automatic
shutdown.

Low Battery delay
(seconds)

Delay in seconds between low-battery alarm and initiation of the
automatic shutdown.