Figure 57: service menu, Figure 58: configure menu, Figure 59: # of upss (total) – MaxPower Corp Gamatronic Power+ M50-RM User Manual
Page 73: Figure 60: # of upss (redundancy)
Gamatronic Electronic Industries Ltd.
POWER+ RM
50
K
VA, N.Am. Std. – User Guide, Release 1.9
57
5. Select
Configure, option 5, to configure the Power+ modules:
[Main Menu > SETUP > (password) > Ent > Service]
1> ------ 4> DryOut Test 7> --------
2> UPSs 5> Configure 8> Powr.Calib
3> ------- 6> En/Dis shar 9> SC2012..
Select, then Enter
Figure 57: Service menu
6. Select
# UPSs (total), option 2, to specify the total number of modules in the system:
[Main Menu > SETUP > (password) > Ent > Service > Configure]
1> # OF UPSs (redundancy) 5> Dry, Alarms
2> # OF UPSs (total) 6> Calibration
3> # OF BATT 7> Parallel/StandAlone
4> Static Switch Setup 8> REM COMMAND
Figure 58: Configure menu
7.
Use the arrow keys to specify the total number of modules installed in the Power+, and
then press Ent:
[Main Menu > SETUP > (password) > Ent > Service > Configure > # OF UPSs (total)]
Set number of UPSs (total)
04 (02 redundant)
Figure 59: # of UPSs (Total)
8. Select
1,
# of UPSs (Redundancy) in Figure 58 to specify the number of modules used
for redundancy:
[Main Menu > SETUP > (password) > Ent > Service > Configure > # OF UPSs (redundancy)]
Set number of UPSs (Redundancy)
01 (04 total)
Figure 60: # of UPSs (Redundancy)
Note: The redundant modules are designated to replace other system modules when they stop
working. For example, a 100-kVA system with 10 modules of which two are configured for
redundancy can deliver a maximum of 80 kVA.