Gamatronic Electronic Industries Ltd.

POWER+ RM

50

K

VA, N.Am. Std. – User Guide, Release 1.9

53

5.11.3

Continue first-time startup

1.

Switch all battery switches "ON" – on the UPS and on all battery cabinets, if any.

2.

You can now turn on the load devices.

3.

After turning on the load devices, verify that you have a normal reading on the display
screen. The display will look similar to Figure 52, but of course your readings will be
different.

LOAD LEVEL ---11:20:25---
L1: _____ 030A, 120V BATTERY: 432V
L2: ______ 024A, 120V UPS OK (ON)
L3: _______ 022A, 120V STSW OK (INV)

Figure 52: Normal display, system under load (3-phase output)

Continue with section

5.12 on page 54.