Figure 274: network menu, Figure 275: network menu, Figure 276: setting the snmp no comm factor – MaxPower Corp Gamatronic Power+ M50-RM User Manual

Page 152: Figure 277: sc2012 menu

background image

Gamatronic Electronic Industries Ltd.

POWER+ RM

50

K

VA, N.Am. Std. – User Guide, Release 1.9

136

11. Select

Store:

[Main Menu > SETUP > (password) > Ent > Service > SC2012 > Network]

1> Set IP ADDRESS 157.211.000.253
2> Set GATEWAY 157.211.000.251
3> Set MASK 255.255.255.000
4> Store 5> SNMP factor Select:1

Figure 274: Network menu

Entered information is stored.

12. Select

SNMP factor:

[Main Menu > SETUP > (password) > Ent > Service > SC2012 > Network]

1> Set IP ADDRESS 157.211.000.253
2> Set GATEWAY 157.211.000.251
3> Set MASK 255.255.255.000
4> Store 5> SNMP factor Select:1

Figure 275: Network menu

13. Use the arrows keys to set the SNMP NO COMM Factor, press Ent and then Esc:

[Main Menu > SETUP > (password) > Ent > Service > SC2012 > Network > SNMP factor]

Set SNMP NO COMM Factor Value
(10 - 99)

50

Figure 276: Setting the SNMP NO COMM factor

14. Select

Reset MBX:

[Main Menu > SETUP > (password) > Ent > Service > SC2012 > Reset MBX]

1> Restart controller 3> Network…
2> Factory settings 4> Reset MBX
Your selection: 1 5> --------------
Enter if you are sure (else press Esc.!)

Figure 277: SC2012 menu

The MBX is reset.