2 changing the power+ output frequency, Changing the power+ output frequency, Figure 48: main menu – MaxPower Corp Gamatronic Power+ M50-RM User Manual
Page 68: Figure 49: level 1 password access, Figure 50: module config. setup menu, Figure 51: setting the module/s frequency
Gamatronic Electronic Industries Ltd.
POWER+ RM
50
K
VA, N.Am. Std. – User Guide, Release 1.9
52
If you need to change the frequency from the default 60 Hz, continue with section 5.11.2;
otherwise, continue with section 5.11.3.
5.11.2
Changing the Power+ output frequency
1.
Press the Enter key to display the main menu, and then select SETUP:
1> SYSTEM 4> HISTORY 7> SETUP
2> UPS MODULE 5> BATTERY 8> STATIC SW
3> SELFTEST 6> ALARM 9> _____
NAVIGATE:
Figure 48: Main menu
2.
Enter the password. (The default password is pressing the "left-arrow" key eight times,
and then the Enter key:
[Main Menu > SETUP]
POWER+ System Setup
Type in Level-1 PASSWORD, THEN – ENTER
Your privilege will expire after 15 min.
PASSWORD:________
Figure 49: Level 1 password access
3. Select
Module/s frequency:
[Main Menu > SETUP > (password) > Module conf.]
1. Num of phase 5.Output Adjust
2. Module/s frequency 6.Frequency Limits
3. Module/s voltage 7.DC Calibration
4. Update Vo/Fr/ph 8.AC Calibration
Figure 50: Module Config. setup menu
4. Use
the
▲▼arrow keys to set the module/s frequency, press Ent, and then Esc:
[Main Menu > SETUP > (password) > Module conf. > Module/s frequency]
--- SET MODULE/S FREQUENCY ---
SELECT – 1 HARD (DIP DEPEND.)
SELECT – 2 SET 50HZ (SELECTED)
SELECT – 3 SET 60HZ
Figure 51: Setting the Module/s frequency
(Do not choose option 1 – HARD).