175
UPS capacity
10 kVA
20 kVA
30 kVA
40 kVA
50 kVA
Dimensions (U.S. measurements) incl. exterior cabinet, excl. batteries
Height
78.4 in. (including cabinet legs)
Width
24 in
Depth
39.1 in
Weight
(lbs)
766 788 811 833 856
Dimensions (metric measurements) incl. exterior cabinet, excl. batteries
Height
1990 mm (including cabinet legs
Width
611 mm
Depth 994
mm
Weight
(kg)
347.4 357.6 367.8 378.0 388.2
Acoustic Noise
Noise (dBA) with half load
48
52
53
54
55
Noise (dBA) with full load
51
54
55
57
58
SYSTEM CONTROLLER – TECHNICAL DATA
Microcontroller core
16 bit
Display
4 × 40 characters LCD with backlight
Other indicators
8 LEDs, buzzer
Analog input channels
3 for battery current measurement
1 for temperature measurement
Voltage-free user input channels
(dry contacts)
8
Real Time Clock (RTC)
Yes (operates for 2 weeks without power)
Power meter
kVA, kW, PF
Volt-free outputs (dry contacts)
6 outputs, rated 50V/1A
RS232 user port
Yes, isolated
Optional communication
TCP/IP, GPRS/SMS wireless communications (optional)
Communications with system modules
Serial, isolated
Events log
255 events
System operation without controller
Unchanged
On-screen parameters
Load bar-graph
3-phase voltages
3-phase currents
Battery voltage
Status of each UPS module
Static-switch parameters and status
Battery sensor temperature
Alarms
(floating output relay contacts,
each rated for max. 48 Vdc 1 A)
Ac failure
Dc failure
UPS module(s) failure
Load on bypass
Battery test failure
Over/under temperature
Overload
Power requirements
3 × 208 Vac / ±216 Vdc 15 W