5 setting temperature compensation, Setting temperature compensation, Figure 190: battery setup menu – MaxPower Corp Gamatronic Power+ M50-RM User Manual
Page 127: Figure 191: temperature compensation setup menu, Figure 192: set temperature compensation
Gamatronic Electronic Industries Ltd.
POWER+ RM
50
K
VA, N.Am. Std. – User Guide, Release 1.9
111
8.10.5
Setting Temperature Compensation
1. Select
Temp Compensat.:
[Main Menu > SETUP > (password) > Battery]
1> Test-Voltage 5> Battery test…
2> Test Alarm 6> Capacity 0020 AH)
3> Current-Limit.. 7> ‘AuTo’ Test
4> Temp Compensat. 8> Enable/Dis Options
Figure 190: Battery setup menu
2. Select
Temperature compensation Value Setup and press Ent:
[Main Menu > SETUP > (password) > Battery > Temp Compensat.]
1> Temperature Compensation Value Setup
2> Disable Temp. Compensation (2.0 mV)
3> Set ABSOLUTE Max & Min Voltages 1
Press ‘2’ to toggle enable / disable
Figure 191: Temperature compensation setup menu
3.
User the arrow keys to set the temperature compensation and press Ent:
[Main Menu > SETUP > (password) > Battery > Temp Compensat. >Ent]
Temperature Compensation Setup
2.0 – 4.0
Compensate : 2.0 mV/°C (Per Cell)
Figure 192: Set temperature compensation