Technical specifications, Echnical specifications – MaxPower Corp Gamatronic Power+ M50-RM User Manual
Page 190
Gamatronic Electronic Industries Ltd.
POWER+ RM
50
K
VA, N.Am. Std. – User Guide, Release 1.9
174
16. T
ECHNICAL SPECIFICATIONS
Table 26: Specifications for the RM 50 kVA N.Am. Std. model
POWER
+
TECHNICAL DATA
Topology
True On-line Battery, Double Conversion, VFI
Construction
Modular parallel hot-plugged modules
Operation Continuous
Input
Voltage
3 × 208 Vac + N (3 x 120 Vac, N = Neutral)
Voltage range
+15 % and -25 %
Current
28 A per module – no inrush current at startup
Frequency
47 Hz – 63 Hz
Power walk-in
< 60 sec.
Power Factor
0.99
THDI
5 %
Output
Rated power for 3-3 configuration:
10 kVA / 8 kW to 50 kVA / 40 kW
Frequency tracking range
±2 Hz
Slew rate
1 Hz / sec
Voltage
3 × 208 Vac + N (3 x 120 Vac, N = Neutral)
Static Regulation
±1 %
Regulation for unbalanced load
±1 % for 100 % unbalanced load
Dynamic resp. to 100% load step
±2 %
Overload
110 % for 10 min., 125 % for 60 sec. 1000 % for 1 cycle
Waveform Sinusoidal
THD
Less than 2 % for linear load
Load CF
4:1
Ac-Ac efficiency (nominal)
Up to 94 % at full load
Dc-Ac efficiency (nominal)
Up to 97 % at full load
Batteries
Dc-Link Voltage
±160 Vdc to ±216 Vdc
Quantity:
In optional external cabinet
32 × 12 Vdc (40 Ah)
2 x 32 x 12 Vdc (40 Ah)
Type
Sealed, lead acid, rechargeable
Typical battery runtime:
with 100 % load:
with 50 % load:
4.5 min.
17 min.
General
Maximum power dissipation (Po=8KW)
N*510W (N*998 BTU), where N = # modules
Ambient temperature
operation:
storage:
+14 to +104 °F (-10 to +40
°C)
-4 to +140 °F (-20 to +60
°C)
Relative humidity
95 % max., non-condensing
Altitude
1500 m without derating
Enclosure IP20
Cooling system
Multi-Fan with speed control (forced)
Standards
EMC
IEC 62040-2, under EMC 2004/108/EC
Design
IEC 62040-3
Safety
IEC 62040-1, under LVD 2006/95/EC
Low magnetic field radiation
EMF as per ICNIRP
All specifications are subject to change without notice.