8 setting the menu language, 9 system parameter settings, 1 first general screen – MaxPower Corp Gamatronic Power+ M50-RM User Manual
Page 160: Setting the menu language, System parameter settings, First general screen, Figure 297: set menu language, Figure 298: select general, Figure 299: general (screen 1)
Gamatronic Electronic Industries Ltd.
POWER+ RM
50
K
VA, N.Am. Std. – User Guide, Release 1.9
144
8.15.8
Setting the Menu Language
Select the desired menu language using the
▲▼ keys and press Ent:
[3-second Esc > Language]
----- LANGUAGE SETUP -----
SELECT - 1: English (selected)
SELECT - 2: Spanish
SELECT - 3: Portuguese
Figure 297: Set menu language
8.15.9
System Parameter Settings
User the arrow keys
▲▼ to select General, and then press Ent:
[3-second Esc]
1> UPSs Stat 5> Dry In/Out Stat
2> UPSs On/Off 6> Alarms Status
3> SoftWare Rev 7> Language
4> Network... 1 8> General
Figure 298: Select General
8.15.9.1
First General Screen
A description of the various system parameters shown in screen 1 are listed below.
[3-second Esc > GENERAL]
ACV:120...ALM:242/185 TEMP. ALARM:45C
MODULES:07/02 C.LIM= off , T.C= 2.0mV
DCV:216...ALM:475/360/340
BATT...TEST:04/05/360/352...CAP: 0010 AH
Figure 299: General (Screen 1)
a.
ACV: nominal value of the input/output ac voltage (220 for 2x32 batteries; 110 for 2x16
batteries).
b.
ALM: input ac voltage alarm HIGH/LOW.
c.
TEMP. ALARM: high temperature limit for an external temperature sensor.
d.
MODULES: QUANTITY/REDUNDANCY: 07/02 in the screen means that 7 modules are
presented in the system, 2 modules are reserve (full load is 10 kVA*(7-2)=50 kVA / 40
kW).
e.
C.LIM.=off (VALUE): battery current limit function is de-activated (off) or maximum
battery current value in Amps. If C.LIM is activated, the system must be equipped with