6 setting disable temperature compensation, 7 setting absolute maximum and minimum voltages, Setting disable temperature compensation – MaxPower Corp Gamatronic Power+ M50-RM User Manual
Page 128: Setting absolute maximum and minimum voltages, Figure 193: battery setup menu, Figure 195: select set absolute max & min voltages
Gamatronic Electronic Industries Ltd.
POWER+ RM
50
K
VA, N.Am. Std. – User Guide, Release 1.9
112
8.10.6
Setting Disable Temperature Compensation
1. Select
Temp Compensat.:
[Main Menu > SETUP > (password) > Battery]
1> Test-Voltage 5> Battery test…
2> Test Alarm 6> Capacity 0020 AH)
3> Current-Limit.. 7> ‘AuTo’ Test
4> Temp Compensat. 8> Enable/Dis Options
Figure 193: Battery setup menu
2. Select
Enable Temp. Compensation and press Ent to toggle enable/disable:
[Main Menu > SETUP > (password) > Battery > Temp.Compensat.]
1> Temperature Compensation Value Setup
2> Enable Temp. Compensation ( OFF)
3> Set ABSOLUTE Max & Min Voltages 1
Press ‘2’ to toggle enable / disable
1> Temperature Compensation Value Setup
2> Disable Temp. Compensation (2.0 mV)
3> Set ABSOLUTE Max & Min Voltages 1
Press ‘2’ to toggle enable / disable
Figure 194: Enable/Disable temperature compensation
8.10.7
Setting Absolute Maximum and Minimum Voltages
1. Select
Set ABSOLUTE Max & Min Voltages:
[Main Menu > SETUP > (password) > Battery > Temp. Compensat.]
1> Temperature Compensation Value Setup
2> Enable Temp. Compensation ( OFF)
3> Set ABSOLUTE Max & Min Voltages 1
Press ‘2’ to toggle enable / disable
Figure 195: Select Set ABSOLUTE Max & Min Voltages