6 setting frequency limits, 7 calibrating dc voltage, Setting frequency limits – MaxPower Corp Gamatronic Power+ M50-RM User Manual
Page 120: Calibrating dc voltage, Figure 168: module config. setup menu, Figure 169: select the frequency limits, Figure 170: module config. setup menu, Figure 171: calibrate positive or negative voltage

Gamatronic Electronic Industries Ltd.
POWER+ RM
50
K
VA, N.Am. Std. – User Guide, Release 1.9
104
8.9.6
Setting Frequency Limits
1. Select
Frequency Limits:
[Main Menu > SETUP > (password) > Module conf.]
1. Num of phase 5.Output Adjust
2. Module/s frequency 6.Frequency Limits
3. Module/s voltage 7.DC Calibration
4. Update Vo/Fr/ph 8.AC Calibration
Figure 168: Module Config. setup menu
2. Using
the
▲▼ keys set the frequency limits, press Ent, and then Esc:
[Main Menu > SETUP > (password) > Module conf. > Frequency Limits]
--- Set frequency limits ---
1: No Change 4: +/- 3Hz
2: +/- 1Hz (slctd) 5: +/- 4Hz
3: +/- 2Hz 6: +/- 0.5Hz
Figure 169: Select the frequency limits
8.9.7
Calibrating DC Voltage
1. Select
DC Calibration:
[Main Menu > SETUP > (password) > Module conf.]
1. Num of phase 5.Output Adjust
2. Module/s frequency 6.Frequency Limits
3. Module/s voltage 7.DC Calibration
4. Update Vo/Fr/ph 8.AC Calibration
Figure 170: Module Config. setup menu
2. Select
either
Calibrate Positive Voltage or Calibrate Negative Voltage and then
press Ent:
[Main Menu > SETUP > (password) > Module conf. > DC Calibration]
--- MODULES DC VOLTAGE CALIBRATION ---
SELECT – 1: Calibrate Positive Voltage
SELECT – 2: Calibrate Negative Voltage
Then press ENTER to continue
Figure 171: Calibrate Positive or Negative Voltage