7 selecting standalone or parallel operation, Selecting standalone or parallel operation, Figure 254: calibrating dc current – MaxPower Corp Gamatronic Power+ M50-RM User Manual
Page 147: Figure 255: entering actual current, Figure 256: service > configure menu
Gamatronic Electronic Industries Ltd.
POWER+ RM
50
K
VA, N.Am. Std. – User Guide, Release 1.9
131
5. Press
Ent to continue:
[Main Menu > SETUP > (password) > Ent > Service > Configure > Calibration > DC-I
Calibration]
1> Calibrate Battery #1 Current
Figure 254: Calibrating DC current
6.
Using the arrow keys, set the actual current and then press Ent:
[Main Menu > SETUP > (password) > Ent > Service > Configure > Calibration > DC-I Calibration
> Ent]
CURRENT METER #01 CALIBRATION
Enter the value of the actual current:
02000 (X0.1)A
Figure 255: Entering actual current
8.12.3.7
Selecting Standalone or Parallel Operation
1. Select
Parallel/StandAlone:
[Main Menu > SETUP > (password) > Ent > Service > Configure]
1> # OF UPSs (redundancy) 5> Dry, Alarms
2> # OF UPSs (total) 6> Calibration
3> # OF BATT 7> Parallel/StandAlone
4> Static Switch Setup 8> REM COMMAND
Figure 256: Service > Configure menu
2. Select
Stand Alone or Parallel by using the
▲▼arrow keys and Ent:
[Main Menu > SETUP > (password) > Ent > Service > Configure > Parallel/StandAlone]
--- Parallel / Stand-Alone Setup ---
SELECT - 1: Stand Alone (selected)
SELECT - 2: Parallel
Figure 257: Setting standalone or parallel operation