beautypg.com

3 the main menu and its options, The main menu and its options, Table 16: main menu options – MaxPower Corp Gamatronic Power+ M50-RM User Manual

Page 165

background image

Gamatronic Electronic Industries Ltd.

POWER+ RM

50

K

VA, N.Am. Std. – User Guide, Release 1.9

149

9.3

The Main Menu and its options

The Main Menu of Power+’s built-in remote management software consists of a column of option
buttons on the left side of the Main Screen (see Figure 304 on page 148).

Table 3 lists the options in the Main Menu column on the Main Screen, and describes each option
briefly. Each option is described in greater detail in the subsequent sections.

Table 16: Main Menu options

M

ENU OPTION

D

ESCRIPTION

Main

Displays a condensed system status: Alarm status and basic readings.

Analysis

Shows real-time readings for each input and output phase: voltage, current,
kVA, kW, and power factor.

Modules

Displays status of individual UPS modules, shows input and output ac
voltages and currents, dc voltage, and active alarms if any.

STSW

Displays status of Static Switch, including inverter output voltages and
frequency, bypass voltages and frequency, and active alarms if any.

Log

Displays system log; data can be printed or exported to an Excel file.

Control

From this screen, the following system commands can be executed: Move
load to bypass, move load to inverter, start battery test, abort battery test,
LEDs test, shutdown, startup, restart, simulate load on battery condition,
simulate battery status is low.

Use of this option is disabled by factory default. To enable (or disable), from
the Power+ console main menu choose the following:
(7) Setup > (8) Service > (5) Config > (8) Rem Command

SMS

View received or sent SMS Messages in this screen from this screen (Wing
module must be present). Click Available SMS commands to send an SMS
message.

Configuration

Configure the settings of the remote management software.

The Main Menu options are described in more detail below.