14 configuration, 1 check configured modules, Configuration – MaxPower Corp Gamatronic Power+ M50-RM User Manual
Page 72: Check configured modules, Figure 54: main menu, Figure 55: password access, Figure 56: setup menu
Gamatronic Electronic Industries Ltd.
POWER+ RM
50
K
VA, N.Am. Std. – User Guide, Release 1.9
56
5.14
Configuration
Perform the following configuration steps from the Control Panel.
5.14.1
Check Configured Modules
Verify that the number of configured modules matches the desired output power, and verify that
the number of redundant modules is correct. Modify as needed.
1. Press
Ent to reach the Main Menu.
1> SYSTEM 4> HISTORY 7> SETUP
2> UPS MODULE 5> BATTERY 8> STATIC SW
3> SELFTEST 6> ALARM 9> _____
NAVIGATE:
Figure 54: Main Menu
2.
From the Main Menu select option 7, Setup.
[Main Menu > SETUP]
POWER+ System Setup
Type in Level-1 PASSWORD, THEN – ENTER
Your privilege will expire after 15 min.
PASSWORD:________
Figure 55: Password access
3.
When the Password access panel appears, enter the password and press Ent. The
factory default password is to press the
key 8 times.
Note: If the password has been changed and the system does not accept it, request from your
system administrator the technician password, which cannot be changed, and use it to
reset the user password.
4. Select
Service, option 8:
[Main Menu > SETUP > (password) > Ent]
1> Alarm set 5> Time 9> Silicon
2> Module conf. 6> Site
3> Battery 7> Password #1
4> Charge 8> Service
Figure 56: Setup menu