3 set date and time and serial number, 4 define the ip address of the power, Set date and time and serial number – MaxPower Corp Gamatronic Power+ M50-RM User Manual
Page 75: Define the ip address of the power, Figure 64: date and time, Figure 65: site number, Figure 66: network menu
Gamatronic Electronic Industries Ltd.
POWER+ RM
50
K
VA, N.Am. Std. – User Guide, Release 1.9
59
5.14.3
Set Date and Time and Serial Number
To verify the date and time set in the System Controller and make sure that they are correct:
1. Use
the and
keys to select the year, month, day, hour, minute, or second you wish
to modify, then use the
and
keys to set the correct value for the selected item.
Press Ent:
[Main Menu > SETUP > (password) > Time]
Set real time
Year Month Day Hour Min Sec
2011 09 30 23 58 00
Figure 64: Date and time
2.
Enter the serial number of the Power+ system in the System Controller, and then press
Ent:
[Main Menu > SETUP > (password) > Site]
Site number: 013271
Figure 65: Site number
Note: The serial number of Power+ is on a bar-code label at the bottom of the unit, on the left
hand side.
5.14.4
Define the IP Address of the Power+
This procedure assigns the Power+ an address within the domain of the customer's computer
network.
1.
Obtain IP, gateway, and mask addresses from the system administrator of the
organization for the Power+ system.
2. Select
Set IP ADDRESS in the Network menu:
[Main Menu > SETUP > (password) > Ent > Service > SC2012 > Network]
1> Set IP ADDRESS 157.211.000.253
2> Set GATEWAY 157.211.000.251
3> Set MASK 255.255.255.000
4> Store 5> SNMP factor Select:1
Figure 66: Network menu