8.12.3.6
Calibrating DC Currents
1. Select
Calibration:
[Main Menu > SETUP > (password) > Ent > Service > Configure]
1> # OF UPSs (redundancy) 5> Dry, Alarms
2> # OF UPSs (total) 6> Calibration
3> # OF BATT 7> Parallel/StandAlone
4> Static Switch Setup 8> REM COMMAND
Figure 250: Service > Configure menu
2. Select
DC-I Offset removal:
[Main Menu > SETUP > (password) > Ent > Service > Configure > Calibration]
1> ----- 5> -----
2> DC-I Offset removal 6> -----
3> DC-I Calibration 7> -----
4> ----- Select
Figure 251: DC-I menu
3.
Follow screen instructions:
[Main Menu > SETUP > (password) > Ent > Service > Configure > Calibration > DC-I Offset
removal]
To remove current offsets,
DISCONNECT BATTERIES and LOAD first,
Then, press ENTER.
Else, press Esc. (0516 0517 0517)
Figure 252: Remove current offsets
4. Select
DC-I Calibration:
[Main Menu > SETUP > (password) > Ent > Service > Configure > Calibration]
1> ----- 5> -----
2> DC-I Offset removal 6> -----
3> DC-I Calibration 7> -----
4> ----- Select
Figure 253: DC-I menu