1 setting number of phases, 2 setting module/s frequency, Setting number of phases – MaxPower Corp Gamatronic Power+ M50-RM User Manual
Page 117: Setting module/s frequency, Figure 156: setup menu, Figure 157: module config. setup menu, Figure 158: module config. setup menu, Figure 159: setting the module/s frequency
Gamatronic Electronic Industries Ltd.
POWER+ RM
50
K
VA, N.Am. Std. – User Guide, Release 1.9
101
2. Select
Module conf.:
[Main Menu > SETUP > (password) > Ent]
1> Alarm set 5> Time 9> Silicon
2> Module conf. 6> Site
3> Battery 7> Password #1
4> Charge 8> Service
Figure 156: Setup menu
8.9.1
Setting Number of Phases
1. Select
Num of phase:
[Main Menu > SETUP > (password) > Module conf.]
1. Num of phase 5.Output Adjust
2. Module/s frequency 6.Frequency Limits
3. Module/s voltage 7.DC Calibration
4. Update Vo/Fr/ph 8.AC Calibration
Figure 157: Module Config. setup menu
8.9.2
Setting Module/s Frequency
1. Select Module/s frequency:
[Main Menu > SETUP > (password) > Module conf.]
1. Num of phase 5.Output Adjust
2. Module/s frequency 6.Frequency Limits
3. Module/s voltage 7.DC Calibration
4. Update Vo/Fr/ph 8.AC Calibration
Figure 158: Module Config. setup menu
2. Use
the
▲▼arrow keys to set the module/s frequency, press Ent, and then Esc:
[Main Menu > SETUP > (password) > Module conf. > Module/s frequency]
--- SET MODULE/S FREQUENCY ---
SELECT – 1 HARD (DIP DEPEND.)
SELECT – 2 SET 50HZ (SELECTED)
SELECT – 3 SET 60HZ
Figure 159: Setting the Module/s frequency